MULTI-STAGE MULTI-OUTLET PUMPS

SPP Pumps is the first company to offer FM Approved multi-stage multi-outlet (MSMO) pumps. Using multiple impellers to generate more head than a single impeller, MSMO pumps are used in fire protection systems in most tall buildings including offices, hospitals and hotels. MSMO pumps offer many benefits: buildings need fewer pumps; pipework and valves are reduced; the need for water storage tanks on intermediate floors is eliminated; and the loading on the building is reduced. The cost and space saving implications are significant: power requirements are lower, pump rooms can be smaller and, in line with new EU legislation, there is no need to use pressure reducing valves to prevent over-pressurisation of sprinkler heads. Driven by electric motors or diesel engines, SPP MSMO pumps are available to satisfy any LPCB specification for automatic sprinkler protection in high rise and multiple storey buildings.

TYPICAL INSTALLATIONS: • Offices • Hotels • Residential Buildings • Tunnels • High Rise Buildings TYPICAL APPLICATIONS:

• Sprinkler systems • Hydrant systems • Deluge systems • Monitor systems • Water curtains

FIRE - MULTI-STAGE MULTI-OUTLET PUMPS

SPP Pumps, Inc. 2905 Pacific Drive Norcross, GA 30071 Tel: (770) 409-3280 www.spppumps.com

FIRE PROTECTION  MULTISTAGE MULTIOUTLET PUMPS

MULTISTAGE MULTIOUTLET PUMPS PER NFPA 20

ELECTIC-DRIVE CONTROLLERS AND ACCESSORIES

PRESSURE - ACTUATED SWITCH: 10.5.2.1.1.2 A dedicated pressure-actuated switch or electronic pressure sensor having adjustable high- and low-calibrated set-points should be provided for all discharge ports, as part of the controller. PRESSURE RECORDER: 10.5.2.1.1.3 A dedicated pressure recorder shall be provided for each discharge port of the pump as part of the controller. This pressure recorder shall record the pressure in each fire pump controller pressure-sensing line at the input of the controller. ENGINE DRIVE CONTROLLERS PRESSURE-ACTUATED SWITCH: 12.7.2.1.1.2 A dedicated pressure-actuated switch or electronic pressure sensor with adjustable high- and low-calibrated set-points shall be provided for each discharge port of the pump as part of the controller. PRESSURE RECORDER: 12.7.2.1.1.3 A dedicated pressure recorder should be installed to sense and record the pressure in each fire pump controller pressure sensing line at the input of the controller. This shall be provided for each discharge port of the pump as part of the controller. The pressure actuated switch described above in 12.7.2.1.1.2, which refers to 12.7.2.1.1.1, does not apply to a non- pressure-actuated controller, where the pressure-actuated switch or pressure responsive means shall not be required.

DEFINITIONS MULTISTAGE MULTIPORT PUMP: 3.3.44.11* A multistage multiport pump is a single-driver pump with multiple impellers. These impellars operate in series where the discharge from each impeller, excluding the last impeller, is the suction for the next impeller. Discharge ports are provided after multiple impellers. THE DIFFERENCE BETWEEN THE MSMO AND FIRE PUMPS ARRANGED IN SERIES: A.3.3.44.11 This pump functions similarly to fire pumps arranged in series. What is the main difference between a multistage multiport pump and fire pumps arranged in series? Pumps arranged in series require individual drivers. Also, there is no shutoff valve between the impellers on a multistage multiport pump. GENERAL REQUIREMENTS SHUTOFF VALVE: 4.8.2 A shutoff valve is not required between the impellers of a multistage multiport pump. DISCHARGE COMPONENTS: 4.16.2 The discharge components for all ports should consist of the following: pipe, valves and fitting that extend from the pump port discharge flange to the system side of the discharge valve for that specific port.

TECHNICAL SPECIFICATIONS • Flow range: 750 gpm

SALIENT FEATURES •

Substantial saving on construction of pump houses • More building space to utilize Multi outlet variant reduces the necessity of multiple pumps for different head requirements • Less pipe work and valv es for building zones No water storage tank on intermediate floors • Self alignment of pump and motor couplings Ring section diffuser type construction totally eliminates the radial loads • The suction/delivery piping can be placed as per the user’s requirement throughout 180 • Low product and maintenance cost

• • • •

Head range: Up to 1640 ft Number of outlets: up to 7 Type of execution: horizontal Standard materials of constructions (Casing/Impeller/Shaft): CI / Bronze /SS

• •

Available in gland pack 50 Hz / 60 Hz availability

FIRE - MULTI-STAGE MULTI-OUTLET PUMPS

SPPMSMOFUS_01PR