HYDRAULIC CONNECTIONS

A: Connecting collectors in parallel with diagonal hydraulic connections

The collectors can be connected in parallel using the joint kit. A maximum of 6 collectors can be connected in parallel per row.

The inlet and outlet connections of the collector array must be arranged in such a way as to form a diagonal connection (with the inlet at the bottom of one side of the array and the outlet at the top of the other side).

B: Connecting collectors in series

A single collector array may be connected in series to another array. It is important that the number of collectors is the same in each row in order to avoid dierences in fl ow rate within the arrays.

C: Connecting collector arrays in parallel

A single collector array may be connected in parallel to another array. It is important that the number of collectors is the same in each row in order to avoid dierences in flow rate within the arrays. Hydraulic connection should be carried out according to the principle of reverse return.