15
e14. _____ After manifold pressure is at proper range, visually inspect burner to ensure low fire flame is not flickering across the burner. The low fire flame should be as small as possible while still propagating all the way across the burner. If flame is large, reduce low fire position on the gas actuator If flame is flickering, increase low fire position on the gas actuator e15. _____Release the clutch on the gas actuator so that the Corel controller can control the actuator e16. _____ Turn off SW6 and SW5 (burner and fans will shut down)
System is now ready for testing from the operator’s remote panel