RTT Booth & AMU Detailed Start-Up Guide

21

Final Checklist

h1. _____ Booth fans start/stop from remote operator panel h2. _____ Booth doors do not blow open during fan startup/shutdown h3. _____ Compressed air solenoid is only energized when booth fans are running, and cure mode is off h4. _____ Exhaust filter manometers are installed and working properly h5. _____ booth balances to 0.000” or slightly negative with exhaust VFD at 55.00hz or less h6. _____ AMU burner ignites consistently without faults from the operator remote panel (winter mode) h7. _____ Booth has run through a minimum of 5 consecutive cure cycles without faults or alarms h8. _____ Caps have been put back on the green and red tubes in the AMU control panel

h9. _____ All gas train test ports are closed and tight h10. _____ All access doors on the AMU are closed h11. _____ Customer/Operators have been trained using steps g1. through g16.

Technician Signature:

Printed:

Customer Signature:

Printed:

Distributor Signature:

Printed: