Smart Touch 3 Oven Start-Up & Commissioning 24 Access.

5. Confirm thermocouple sensor is mounted in a location where it will receive airflow, but not in ductwork or too close to any support steel. Ensure wire type to thermocouple is type J – no other wire type is allowed to thermocouple.

Zone 1 Thermocouple properly installed and wired _____ Zone 2 Thermocouple properly installed and wired _____

6. Ensure exhaust fan damper (if equipped) is set in approximately the halfway position.

(Example Photo)

Zone 1 Damper installed and properly adjusted _____ Zone 1 Damper installed and properly adjusted _____