SCOLMORE GROUP/CLICK LITEHOUSE HEAD OF TECHNICAL ENGAGEMENT JAKE GREEN EXAMINES RCDS AND THE NECESSITY OF A TIME-DELAY DEVICE WHEN SELECTIVITY BETWEEN DEVICES IS NEEDED… RCDs and their application

The principle of operation of an RCD is well understood. The live conductors are wrapped around a toroid that is readily magnetised and demagnetised and, while the current in each live conductor remains the same, no magnetic circuit is formed. Should there be an imbalance between the current in the live conductors, usually caused by a current to earth, then a sensing coil ‘picks up’ the newly-formed magnetic circuit and a trip is operated (see Figure 1).

Type AC The AC type RCD is intended only for those circuits where there are no DC components. This limits their selection to those circuits that are purely resistive. The impact of constantly-applied smooth DC will be to saturate the iron core of the current transformer within the RCD, which will thus become insensitive to any further residual currents. The RCD will in effect ‘become blind’ and cease to provide additional protection. Furthermore, research shows that where a 50Hz fundamental frequency has an additional, higher frequency component (for example, 500Hz, 1,000Hz, or 2,000Hz), the Type AC RCD may struggle to operate at the rated residual operating current (I_ Δn). Type AC RCDs are not recommended for general use (531.3.1.1) or for use in new electrical installations (531.3.3). Most manufacturers, including Scolmore, in the UK do not produce Type AC RCDs.

RCD

Load

Type A Type A RCDs are to be used for alternating and pulsating DC, possibly including the presence of smooth residual DC up to 6 mA (Note 1 531.3.3). However, as with the Type AC device, once higher frequency components exist, then the Type A RCD may struggle to

Coil

L

N

R

T = 20 ms

E

Figure 3: DC component.

Circuit protective conductor (cpc)

Figure 1: Basic operation of an RCD.

Type F A Type F RCD is a variant on a Type A device having altered frequency characteristics. This allows for greater sensitivity to higher frequencies. Type F RCDs conform to the requirements of IS EN 62423: 2012. This standard was further amended in 2021. As detailed in IS EN 62423, Type F RCDs are ‘intended for installations when frequency inverters are supplied between phase (line) and neutral or phase (line) and earthed middle conductor and are able to provide protection in case of alternating residual sinusoidal at the rated frequency, pulsating direct residual currents and composite residual currents that may occur’. (Note 2 531.3.3) Type F RCDs will trip when a significant proportion of the supply contains a frequency of up to 1,000Hz. However, once a significant proportion of the applied waveform contains frequencies higher than 1,000Hz, the Type F RCD may struggle to operate at the rated residual operating current (I_Δn). A Type F RCD having I_Δn not exceeding 30mA will meet the requirements of Regulation 722.531.3.101 for protection against electric shock by automatic disconnection of supply (ADS) when used in conjunction with a residual current detecting device (RDC-DD) complying with IS IEC 62955 and as recommended by the manufacturer of the charging equipment. operate at the rated residual operating current (I_Δn). A Type A RCD having I_Δn not exceeding 30 mA will meet the requirements of Regulation 722.531.3.101 for protection against electric shock by automatic disconnection of supply (ADS) when used in conjunction with a residual current detecting device (RDC-DD) complying with IS IEC 62955 and as recommended by the manufacturer of the charging equipment.

The typical structure of RCDs of Type AC, Type A and Type F is detailed in Figure 2.

PE

L2 L3 N

RCD

CT

Relay

EC - Electronic matching system

Load

Figure 2: Voltage independent RCD.