FOCUS ON:
POWER SUPPLY & DISTRIBUTION
Type B Type B RCDs are typically voltage-dependent devices (see Figure 4). A Type B RCD has the same tripping characteristics as a Type F device and additionally: • For residual sinusoidal AC up to 1,000Hz
PE
L1 L2 L3 N
EC - Electronic matching system
RCD
CT1
Relay
CT2
• For residual AC superimposed on a smooth DC • For residual pulsating DC superimposed on a smooth DC • For residual pulsating rectified DC which results from two or more phases • For residual smooth DC, whether suddenly applied or slowly increased independent of polarity. (531.3.3). A Type B RCD having I_Δn not exceeding 30 mA will meet the requirements of Load
EC-B
EC-B - Electronics system to ensure tripping in the case of smooth DC residual current
Figure 4: Voltage dependent RCD.
Regulation 722.531.3.101 for protection against electric shock by automatic disconnection of supply (ADS) and does not require to be used in conjunction with a residual current detecting device (RDC-DD). Figure 5 details the RCD types and their associated symbols along with their properties and relevant standard. (*1)
Standards: Sinusoidal AC with rated frequency
RCD Type
Symbols
Sensitivity to residual current
Properties
Standards
Sinusoidal AC with rated frequency Sinusoidal AC and pulsating DC up to 6 mA Sinusoidal AC and pulsating DC up to 10 mA
BS EN 61008 BS EN 61009 BS EN 61008 BS EN 61009
Alternating
AC
Alternating and pulsating direct current
A
Alternating and pulsating direct current Alternating and pulsating direct current and flat direct current
BS EN IEC 60755 BS EN 62423 BS EN 62423
F
B
All kinds of current up to 1 kHz
Figure 5: RCD types, symbols, properties and standards.
Time-delay RCDs A time-delay RCD (typically, S Type) is specially designed to attain a predetermined value of limiting non-actuating time, corresponding to a given value of residual current (IS EN 61008-1; IS EN 61009-1). An S Type RCD operates more slowly than a non-time delay device and minimises the risk of unwanted operation. However, this benefit means that, as such, an RCD is not permitted to be used as a means of additional protection. S Type devices are necessary where it is required for
S Type RCD
Ratio of 3:1 100mA S Type upstream of 30mA RCD
30mA RCD
30mA RCD
Point of fault selectivity to be achieved between RCDs. Where selectivity is required, Regulation 536.4.1.4 states that selectivity occurs under the following conditions: • The upstream RCD is of a selective type (Type S typically), and • The ratio of the rated residual operating current of the upstream RCD to that of the downstream RCD is at least 3:1. The practical working out of this means that a 30mA device would require a minimum of a 100mA Type S RCD upstream to provide selectivity. Figure 6: Selectivity between RCDs. As part of its Elucian range, Click Scolmore has produced a series of time delay (S Type) RCDs (63 A, 80 A and 100 A) which provide the necessary selectivity for suitably rated downstream devices. Conclusion Great care should be taken by the designer and installer to ensure the correct type of RCD is selected and erected for a specific application. An S Type device is essential when selectivity is required. When in doubt, contact the manufacturer.
Want to know more?
T: +353 (0)1 2811 122 E: sales@clicklitehouse.ie www.clicklitehouse.ie
There is an error in Note 3 of Regulation 531.3.3 I.S. 10101 in that a Type B device is able to operate where alternating currents are superimposed on direct current of 10 mA (not 6 mA as stated). Refer IS EN 62423 clause 8.2.1.2. The non-actuating time is the maximum delay during which a value of residual current higher than the residual non- operating current can be applied to the RCCB without causing it to operate (IS EN 61008; IS EN 61009).