Air Makeup Unit Technical Training Manual

Section 6

Typical Sequence of Operation

After damper is proven open, the Carel controller starts the fan VFDs After the VFDs reach their minimum run speed, they send a signal back to the Carel controller to prove they are running.

If VFDs do not prove, “Blower Start Fault” will be displayed on Carel Controller

With the fans running, 120vac power is sent through the proving switch that looks at air pressure across the burner.

Burner

Pressure must be in this range for proper operation: Minimum: .5”w.c. Maximum: .7”w.c.

Adjustable Profile Plates

Elongated Screw Slots

Fixed Profile Plates

If air switch does not prove, “Low Air Flow Fault” will be displayed on Carel Controller

Side View

Front View

Figure 2