Air Makeup Unit Technical Training Manual

Section 6

Typical Sequence of Operation

If 120vac passes through high gas pressure switch and high temperature limit, it will reach the Fireye Flame controller which will initiate the burner ignition sequence: 1. Energize Igniter 2. Energize Pilot Solenoid 3. Check for Flame Signal 4a. Flame Signal Proven – Energize Main Gas Valves, and De-energize Pilot & Igniter

Normal Operation Flame Fail PTFI Flame Fail Auto Flame Fail MFTI False Flame Idle

4b. Flame Signal Not Proven – De-energize Pilot Solenoid and Igniter, then issue Alarm

If flame signal is not proven, “Flame Safeguard Fault” will be displayed on Carel Controller

Made with FlippingBook - professional solution for displaying marketing and sales documents online