Section 6

Alarm Screen: This screen is accessed if an alarm condition exists (pressing blinking alarm symbol) or it can be accessed from the main menu. Some alarms require acknowledgement in order to silence the alarm horn and/or reset the alarm. Press and HOLD the alarm key in order to acknowledge an alarm. If the alarm is based upon a direct external input from a sensor or external safety control (for example a motor overload), the alarm will remain active (key will blink red) until the external input is corrected. In other cases where the c.pCO module is acting as the safety device, holding the alarm key for a slightly longer duration will reset the alarm condition. Two “Sampled Values” will also be displayed. These values show the state of the named value at the time the alarm is triggered.