Section 5
Effective Duct Length
100% effective duct length
To calculate 100 % effective duct length, use a minimum of 2 1/2 duct diameters for velocities 2500 FPM or less. Add 1 duct diameter for each additional 1000 FPM
Equivalent duct diameter is equal to ( 4ab/ ) 0.5