TABLE - 66
MAXIMUM D.C. RESISTANCE OF CONDUCTOR AND ARMOUR FOR XLPE INSULATED CABLES
Maximum D.C. Resistance per km of cable at 20 °C
Nominal Cross- sectional area of conductor
Aluminium wire armour Galvanized Steel Wire armour 0.6/1.0 kV 1.9/3.3 kV 0.6/1.0 kV 0.6/1.0 kV 1.9/3.3 kV 0.6/1.0 kV 0.6/1.0 kV Single core Single core Two core Three core Four core Five core
Copper conductor
Aluminium conductor
mm²
ohm ohm ohm ohm ohm ohm ohm ohm ohm
1.5
12.1
-------
-------
-------
10.2
9.5
-------
8.8
8.2
2.5
7.41
-------
-------
-------
8.8
8.2
-------
7.7
6.8
4
4.61
-------
-------
-------
7.9
7.5
-------
6.8
6.2
6
3.08
-------
-------
-------
7.0
6.7
-------
4.3
3.9
10
1.83
-------
-------
-------
6.0
4.0
-------
3.7
3.4
16
1.15
1.91
-------
-------
3.7
3.5
1.9
3.1
2.2
25
0.727
1.20
-------
-------
3.7
2.5
1.7
2.3
1.8
35
0.524
0.868
-------
-------
2.6
2.3
1.4
2.0
1.6
50
0.387
0.641
1.30
0.75
2.3
2.0
1.3
1.8
1.1
70
0.268
0.443
0.75
0.67
2.0
1.8
1.2
1.2
0.94
95
0.193
0.32
0.67
0.61
1.4
1.3
1.1
1.1
-------
120
0.153
0.253
0.61
0.42
1.3
1.2
0.76
0.76
-------
150
0.124
0.206
0.42
0.39
1.2
0.78
0.71
0.68
-------
185
0.0991
0.164
0.38
0.37
0.82
0.71
0.65
0.61
-------
240
0.0754
0.125
0.34
0.34
0.73
0.63
0.59
0.54
-------
300
0.0601
0.100
0.31
0.31
0.67
0.58
0.55
0.49
-------
400
0.0470
0.0778
0.22
0.22
0.59
0.52
0.50
0.35
-------
500
0.0366
0.0605
0.20
0.20
-------
-------
-------
-------
-------
630
0.0283
0.0469
0.18
0.18
-------
-------
-------
-------
-------
800
0.0221
0.0367
0.13
0.13
-------
-------
-------
-------
-------
1000
0.0176
0.0291
0.12
0.12
-------
-------
-------
-------
-------
52 MKK XXS002-02/01-12-2014
Made with FlippingBook Annual report