Liberty Weld Cell User & Maintenance Manual

15) It may take a few minutes for the heat detector to cool down.

16) Turn power back on at the Disconnect.

17) Use a can of smoke or lit cigarette to activate the smoke detector located in the valve compartment. The behavior should follow the process noted in Table 1. This verifies the smoke detector is working. Make sure the power is applied to the terminals to activate the suppression agent generator.

18) Turn power off at the Disconnect.

19) The smoke detector may need to be blown out with compressed air to reset.

20) Turn power back on at the Disconnect.

21) Reconnect the wiring connection in the electrical panel for the suppression agent generator(s). Failure to do so will prevent discharge of the fire suppression agent.

Copyright © Clean Air Industries , Inc.

Liberty WeldCell User Manual, August 2023

Page 36 of 66