AMP 2019-2029

Electricity Asset Management Plan 2019-2029

188

Vector Limited://

DESCRIPTION

DISCUSSION OF OPTION

ESTIMATED COST (NPV IF APPLICABLE)

STATUS

Option 1: Do nothing – do not undertake civil and structural upgrades

By postponing or not undertaking the works will result in further deterioration of buildings and structures and this will in turn result in remedial works becoming more extensive and more costly to remedy. Apart from the afore mentioned, Vector is obliged to comply with Council seismic standards within a certain time frame Timely remedial capital investment will remove the risk of further deterioration of zone substation facilities and will also reduce the risk of failure of primary and/or secondary plant inside a zone substation(s) due to failing facilities. Selecting this option also means that we will comply with regulatory and Council seismic requirements to mitigate the risk posed by non-compliant facilities during a seismic event and will then also remove the commensurate risk to operating and maintenance personnel

Rejected

Option 2: Undertake civil and structural remedial capital works

$3.83M Selected

PROPOSED INVESTMENT SUMMARY ($MILLION NOMINAL)

DESCRIPTION

FY20

FY21

FY22

FY23

FY24

FY25

FY26

FY27

FY28

FY29 TOTAL

Auckland civil structures upgrades

0.30

0.54

0.54

0.14

0.14

0.14

0.14

0.14

0.14

0.14

2.36

Northern civil structures upgrades

0.20

0.14

0.14

0.14

0.14

0.14

0.14

0.14

0.14

0.14

1.46

Total CAPEX

0.50

0.68

0.68

0.28

0.28

0.28

0.28

0.28

0.28

0.28

3.82

NEUTRAL EARTHING RESISTOR INSTALLATIONS IN ZONE SUBSTATIONS

NEEDS STATEMENT Our larger commercial and industrial customers have come to depend more and more on reliable electricity as an essential resource for their enterprises and we have had specific requests for 11kV bus sections at certain zone substations to be operated closed (in parallel) to ensure that supply to a customer is uninterrupted in the event of failure of one of Vector’s zone substation transformers, 11 kV bus sections or failure of one of the customer’s 11 kV supply circuits. Because of the fact that we still have a sizable population of older generation 11kV distribution cables with low rated earth screens parallel operation of 11 kV zone substations busbars is not possible at such zone substations due to the risk of more extensive damage to 11kV cables with low rated earth fault currents. On some urban 11 kV systems earth fault currents are up to 15% higher than phase fault currents and can be higher than the 250 MVA (13.1 Kiloampere) rating of typical ring main units. Neutral earthing resistors are used to limit earth fault currents in power systems. The primary effect of the installation of neutral earthing resistors is a very large decrease in the fault current when an earth fault occurs on the system. To be able to provide uninterrupted supply to large customers in the event of 11 kV bus, power transformer or 11 kV supply cable failures there is a need to install neutral earth resistors at such zone substations. Not all zone substations where this plant might be required have been identified yet so this is a capital provision that will be used as and where required.

TARGETED OUTCOMES

CUSTOMER EXPERIENCE

SAFETY

RELIABILITY

RESILIENCE

OPERATIONAL EFFICIENCY

CYBER SECURITY AND PRIVACY

OPTIONS CONSIDERED Options to address the need identified above have been assessed and are summarised in the following table.

Made with FlippingBook - professional solution for displaying marketing and sales documents online