Electricity Asset Management Plan 2019-2029

271

Vector Limited://

Meets Vector security criteria when combined with 11kVbackup

Sandringham Simpson Road Snells Beach South Howick

92 93 94 95 96 97 98 99

23

24 N-1

21

95%

24

100% No constraintwithin +5 years

Meets Vector security criteria

6 8

- N - N

6 8

- -

- -

No constraintwithin +5 years No constraintwithin +5 years

Constraint relieved by the installation of a network battery Meets Vector security criteria when combined with 11kVbackup Constraint relieved by the installation of thesecond transformer Meets Vector security criteria when combined with 11kVbackup

30 13 23 20 17 12 23 18

24 N-1 switched - N-1 switched 21 N-1 switched

22 15 21 34 17 12 11 16

125%

24 24 21 24 14 24 18 24 24 24

122% No constraintwithin +5 years 68% No constraintwithin +5 years 110% No constraintwithin +5 years 86% No constraintwithin +5 years 116% No constraintwithin +5 years No constraintwithin +5 years 99% No constraintwithin +5 years 114% No constraintwithin +5 years 47% No constraintwithin +5 years 91% No constraintwithin +5 years 86% No constraintwithin +5 years No constraintwithin +5 years 84% No constraintwithin +5 years No constraintwithin +5 years 77% No constraintwithin +5 years No constraintwithin +5 years 69% No constraintwithin +5 years 132% No constraintwithin +5 years 124% No constraintwithin +5 years 91% No constraintwithin +5 years 108% No constraintwithin +5 years 61% No constraintwithin +5 years 94% No constraintwithin +5 years 136% No constraintwithin +5 years 104% No constraintwithin +5 years

Spur Road StHeliers

-

111%

Meets Vector security criteria

St Johns

24 N-1

85%

Meets Vector security criteria when combined with 11kVbackup

SunsetRoad

14 N-1 switched

118%

Meets Vector security criteria Meets Vector security criteria

Swanson

100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120

- N

-

-

Sylvia Park Takanini Takapuna

24 N-1

94%

Constraint relieved by transformer capacity upgrade

18 N-1 switched

102%

Constraint relieved by the installation of thesecond transformer

9

- N

9

-

Constraint relieved by transformer capacity upgrade

TeAtatu

22 21

14 N-1 switched

22 16

157%

Meets Vector security criteria Meets Vector security criteria Meets Vector security criteria

TePapapa

24 N-1

87%

Torbay

9

- N

9

-

-

TriangleRoad

15

12 N-1 switched

15

124%

18

Constraint relieved by load transfer to theCBD 22kVdistribution network

Victoria Waiake Waiheke

22

22 N-1 switched

17

102%

22

Meets Vector security criteria Meets Vector security criteria Meets Vector security criteria

9

- N

9 3 8

-

-

11

15 N-1

76%

15

Waikaukau Waimauku Wairau Road Warkworth Wellsford Westfield

9

- N - N

- -

-

Constraint relieved by transformer upgrade+11kVcableproject Meets Vector security criteria when combined with 11kVbackup Constraint relieved by theOmaha substatiob and theBESS atSnells Beach and Warkworth South

11 20

11 20

18 16

16 N-1 switched

124%

20

18 N-1 switched

20

112%

18

Meets Vector security criteria

8

9 N-1

8

93%

9

Meets Vector security criteria when combined with 11kVbackup

25 11 30 42 10

24 N-1 switched

21 11 17 21 10

104%

24 24 32 43

Meets Vector security criteria Meets Vector security criteria

Westgate

24 N-1 32 N-1 43 N-1

45% 92%

WhiteSwan

Constraint relieved by newWiri West substation

Wiri

100%

Meets Vector security criteria

Woodford

- N

-

-

No constraintwithin +5 years

ยน Extend forecastcapacity table as necessary to disclose all capacity by each zone substation