PRODUCT CATALOGUE 2022 | alre.de

Electronic climate controller with timer KTRRUu – 230 VAC Flush-mounted installation – Design Berlin UP

Technical data

Application

Design:

Berlin UP (flush-mounted) PC, PMMA, ABS plastic

Flush-mounted controller with timer function for heating/cooling regulation of 2- and 4-pipe systems used in hotels, homes and offices. The adaptation takes place in a menu. The unit can control up to 5 valve actuators (normally open or normally closed) per output. In 2-pipe operation, the operating mode can be changed via an external contact (changeover) or a temperature sensor. The clock can serve as a master for other controllers for switching to ECO mode. It is possible to activate the energy saving (ECO) or frost protection (OFF) functions via an external contact. Alternatively, the controller”s inputs can be configured to connect with an external temperature sensor or dew point sensor (TPS).

Housing material:

Ambient temperature: Storage temperature: Permissible atmospheric humidity:

0 … 40 °C

−20 … +70 °C

max. 95% rel. humidity, non-condensing

Protection rating: Safety and EMC:

IP 30

according to DIN EN 60730

Max. power consumption: approx. 1 W (2.2 VA) Max. switching current: 3 (0.5) A each Switching element: 2 relays Switching contact: 2 NO contacts Output signal:

Switching, analogue 0…10 V max. 5 mA for activating an rpm-controlled fan NTC internal, optional exter- nal “Sensor 2”* For automatic switching of the controller to heating or cooling mode depending on the inflow temperature (“Sensor 2”); alternatively, this input can be used as an H/C changeover contact upon closing the contact, the ECO function is actuated

Sensor:

A 0 … 10 V interface can be used to control the speed of a fan (EC fan) .

External flow sensor (H/C sensor):

General: Digital rocker switch single-room climate con- troller with timer; optional external dew point sensor; ECO function, ECO value adjustable; “ECO” display; “on/off” display; “heating” dis- play; “cooling” display; “cooling interruption due to condensation”; digital actual value display; backlighting; operating mode “off with frost protection monitoring”; child-safe features; facilities; power-reserve (3 days); actual value correction/measured value correction; learning function; emergency operating mode; holiday setting; party setting; automatic adjustment to summer/winter time; external setting; comfort- able operation using touch-sensitive buttons with dynamic button assignment. Special colours are available for projects as well as the colors anthracite and aluminum on request.

ECO contact:

Control range: Setting range:

5 … 40 °C

Standard setting range for heating (5 … 30 °C), second setting range for cooling (18 … 40 °C)

Hysteresis:

approx. 1 K adjustable

Neutral zone: Display type:

illuminated graphical display

Pipe system compatibility: 2-pipe and 4-pipe

Type/image

Item no.

Features

Circuit diagram PG

KTRRUu 217.456#21 (230 VAC)

Surface finish: glossy Housing colour: pure white like RAL 9010 Operating voltage: 230 VAC, 50 Hz Electrical connection: pluggable screw-type termi- nals, voltage supply side 0.75–2.5 mm², low-volt- age side 0.08−1.5 mm² Mounting/Attachment: in flush-mounted socket – adaptable with cover 50 x 50 mm in almost all rocker switch ranges (deep flush-mounted socket recommended) Protection class: II Max. switching voltage: 230 VAC, 50 Hz Min. switching voltage: 230 VAC, 50 Hz Switching power: 690 W Output signal: switching heating, cooling, heating/ cooling, ECO, OFF, 230 VAC, 50 Hz; analogue 0 … 10 V (5 mA) for activating an rpm-controlled fan Scope of delivery: controller, cover 50 x 50 mm, pure white (like RAL 9010), glossy, alre frame “Berlin”

UA220000

I

* A menu setting can be used to select whether control should be based on the internal or external sensor. In the intermediate positions, if both sensors are used, a weighting is applied to the internal room sensor and the external radiation sensor. The weighting allows for compensation of different struc- tural conditions such as large window areas or cardinal directions. For very slow controlled systems, it is recommended to assign a higher weighting to the radiation sensor than to the internal room sensor.