Single-stage plant room thermostats JET-110/-120 Capillary system – External sensors – Configurable hysteresis
Technical data
Application
Colour:
grey (lower part like RAL 7016, upper part like RAL 7035) Max. 95% rel. humidity, non-con- densing
Control or monitoring of the tem- perature in the industrial domain in a non-aggressive environment, for example, for controlling heating or cooling systems in greenhouses, industrial and sports halls, air-inflated domes, cold storage and refrigeration rooms.
Permissible atmospheric humidity:
Operating voltage:
none
Max. switching current: Min. switching current: Max. switching voltage: Min. switching voltage: Switching element: Switching contact: Control function: Electrical connection: Mounting/attachment:
10 (4) A 150 mA
230 VAC, 50 Hz 24 VAC, 50 Hz
The JET-110 RF is particularly suit- able as an external thermostat.
microswitch
toggler, potential-free heating or cooling screw-type terminals
For successor types for JET-4x and JET-4x F see page 156 (plant room thermostat RTKSA)
wall mounting
Protection class: Protection rating: Safety and EMC:
I
IP 65
according to DIN EN 60730
Sensor:
liquid-filled capillary
Sensor material: General features:
Cu
Scale: degrees Celsius
Type
Item no.
Control range Max. sensor temperature
Hysteresis (approx.)
Ambient temperature
Features
PG
JET-110 R
JA045100
−35 … +30 °C
35 °C
2 … 20 K adjustable 2 … 20 K adjustable 2 … 20 K adjustable 2 … 20 K adjustable
−35 … +35 °C External setting with range restriction, TR −35 … +35 °C Internal setting with viewing window, TW −35 … +70 °C External setting with range restriction, TR −35 … +70 °C Internal setting with viewing window, TW
II
JET-110 RF
JA045200
−35 … +30 °C
35 °C
II
JET-120 R
JA046100
0 … 60 °C
70 °C
II
JET-120 RF
JA046200
0 … 60 °C
70 °C
II
TR = temperature controller, TW = temperature monitor
JET-1.
JET-1x0 RF
JET-1.
Catalogue 2022 | Page 167