Single-stage capillary thermostats JET-1
Technical data
Application
Housing colour:
grey (lower part like RAL 7016, upper part like RAL 7035) Cu (capillaries made from V2A) 1.8 m (for types with “G” in the type specification: 4.5 m)
Monitoring or control of tempera- tures of non-aggressive, liquid and gaseous media. Particularly suitable for wall mounting. The SW-200-12 protecting coil is to be used for temperature control of non-aggres- sive gases in ducts; for temperature control in non-aggressive fluids, use the TH immersion sleeve, and in aggressive fluids, the NTH immersion sleeve. Immersion sleeves or protection coils are not a part of the scope of delivery (see “Accessories/Miscel- laneous” chapter).
Sensor material: Capillary length:
Ambient temperature: Max. sensor temperature Permissible atmospheric humidity:
−20 … +55 °C
top scale value +15%
Max. 95% rel. humidity, non-con- densing
Operating voltage:
none
Max. switching current: Min. switching current: Max. switching voltage: Min. switching voltage: Switching element: Switching contact: Electrical connection: Mounting/attachment:
10 (4) A 150 mA
230 VAC, 50 Hz 24 VAC, 50 Hz
microswitch
toggler, potential-free screw-type terminals
wall mounting
Protection rating: Protection class: Safety and EMC:
IP 65
I
according to DIN EN 60730
Sensor:
liquid-filled capillary
General features:
scale: degrees Celsius, mechani- cal range restriction when external setting is used
Type
Item no.
Control range
Hysteresis adjustable (approx.):
Sensor a x l
Features
PG
JET-110X
JA040100
−35 … +30 °C
2…20 K 9.6 x 122 mm external setting/TR*
II
JET-110XF
JA040200
−35 … +30 °C
2…20 K 9.6 x 122 mm internal setting/TW*
II
JET-120X
JA041100
0 … 60 °C
2 … 20 K
9.6 x 122 mm external setting / TR*
II
JET-120XG
JA041101
0 … 60 °C
2 … 20 K
9.6 x 122 mm external setting / TR*
II
JET-120XF
JA041200
0 … 60 °C
2 … 20 K
9.6 x 122 mm internal setting / TW*
II
JET-130X
JA042100
40 … 100 °C
2 … 20 K
9.6 x 122 mm external setting / TR*
II
JET-130XG
JA042101
40 … 100 °C
2 … 20 K
9.6 x 122 mm external setting / TR*
II
JET-130XF
JA042200
40 … 100 °C
2 … 20 K
9.6 x 122 mm internal setting / TW*
II
JET-133X
JA042300
40 … 100 °C
9.6 x 122 mm external setting/TB**
II
JET-133XF
JA042400
40 … 100 °C
9.6 x 122 mm internal setting / TB**
II
JET-140X
JA043100
70 … 130 °C
2 … 20 K
9.6 x 122 mm external setting / TR*
II
JET-140XF
JA043200
70 … 130 °C
2 … 20 K
9.6 x 122 mm internal setting / TW*
II
JET-143XF
JA043400
70 … 130 °C
9.6 x 122 mm internal setting / TB**
II
JET-150
JA044100
100 … 280 °C
8 … 50 K
6 x 80 mm
external setting / TR*
II
JET-150F
JA044200
100 … 280 °C
8 … 50 K
6 x 80 mm
internal setting / TW*
II
JET-153
JA044300
100 … 280 °C
6 x 80 mm
external setting / TB**
II
JET-153F
JA044400
100 … 280 °C
6 x 80 mm
internal setting / TB**
II
TR = temperature controller, TW = temperature monitor, TB = temperature limiter
* Control function heating or cooling ** C ontrol function heating or cooling, locks when temperature rises, manual reset after temperature fall of at least 8 K
Accessories
Immersion sleeves for types with “X” in the type specification: TH / NTH-140 see page 220 Immersion sleeves for types without “X” in the type specification: TH / NTH-100 / 200 / 280 see page 220 Protection coil for all types: SW-200-12 see page 218 – 219
Catalogue 2022 | Page 168