Understand how the RTT Filter Monitor Pro helps simplify spray booth maintenance. This guide explains how the system monitors filter pressure, displays real-time pressure readings, and provides visual alerts when filters require maintenance. Learn how pressure sensors, transmitters, and adjustable set points work together to track filter loading, helping maintain proper airflow, improve booth performance, and reduce unexpected downtime.

RTT Finishing Solutions 2975 Discovery Blvd. Rockwall,Texas 75032

FILTER MONITOR PRO OPERATION MANUAL

1

Phone: Email:

888-452-6684

sales@rttsolutions.com Website: www.rttsolutions.com

General Overview

The RTT Finishing Solutions Filter Monitor Pro is designed to give operators and managers visual indication when filter maintenance is required. It includes 3 user adjustable set points for each sensor (filter stage) being monitoring. The pressure readings are gathered by an external pressure transmitter (sensor) that is installed near the filters. The pressure transmitter uses poly tubing to connect to pressure ports mounted in the wall of the filter chamber. When the fan is turned on, a pressure differential is created from the front side of the filter to the back side of the filter. As the filter loads with overspray, the pressure differential increases. The transmitter converts the pressure differential into a zero to ten volt DC signal that is sent back to the Filter Monitor Pro which is then converted into a numerical value and displayed on the touch screen.

The pressure that the sensor is designed to read is measured in Inches of Water Column shown as “w.c.. This is a very low pressure range as there are approximately 28 inches of water column in one P.S.I. which means the sensor is reading well below 1 P.S.I.

When the pressure across the filter increases, the value and gauge displayed on the touch screen increase. When the pressure exceeds the “Warning” set point, the screen and the stack light at the top of the controller will turn yellow alerting the operator that the filters will need to be replaced soon. The operator must acknowledge this warning in order to clear the screen. The acknowledgement is recorded in the Operation History Section. When the pressure exceeds the “Replacement Required” set point, the screen and the stack light at the top of the controller will turn red alerting the operator that the filters are in need of replacement. This page also requires the operator to acknowledge the notification and is recorded in the Operation History Section. If the filters are not replaced, and the pressure continues to rise, a final “Shutdown” warning will occur which will de-energize the included dry contact interlock. The interlock can be used to turn off spray equipment, turn on alarm sirens, shut down conveyors, or many other functions that may be required per application.

The Filter Monitor Pro includes a built in ethernet port that can be connected to an active internet connection allowing email and text notifications to be sent when the “Replace Soon” and “Replacement Required” alerts are triggered.

2

Table of Contents

Overview

Pages 04 to 06

Description of tabs

4 5 6

Overview tab

History tab

Settings

Pages 10 to 16

Logging in

10 12 13 14 15 16

Setting pressure set points

Change passcodes Email contacts editor

Timers

Network settings & date/time adjustment

History Features

Pages 07 to 09

View operation history

7 8 9

View pressure chart recordings View pressure graph recordings

Certifications

Page 18

UL 508a

18

3

Tab Based Navigation The tabs located at the top of the screen allow for easy navigation between menus. The tabs remain visible during basic navigation so that its easy to get back to the “Home Screen” if the user gets lost.

5.

1.

2.

4.

3.

1. Overview – Select this tab to go to the overview page that shows all chambers on one screen. 2. Home – Select this tab at any time to return to the chamber 1 home screen. 3. Settings – Select this tab to go to the login screen to adjust various settings such as pressure set points and email notifications. 4. History – Select this tab to view the operation history of the filter monitoring unit. 5. Next – If monitoring more than one chamber, a next tab will be shown here to allow the operator to move to the next chamber being monitored.

4

Overview Tab

This tab displays the name, current pressure, and pressure set points for each sensor connected to the filter monitor controller.

2.

3.

4.

5.

1.

1. Chamber Names – Lists the user entered names of each sensor. 2. Current Pressure – Shows the pressure reading coming from each sensor.

3. Warning Set Point – Shows the pressure at which the yellow warning indicator will be illuminated. 4. Replace Set Point – Shows the pressure at which the red warning indicator will be illuminated. 5. Shutdown Set Point – Shows the pressure at which the interlock for any existing equipment will be de- energized.

5

History Launch Tab

This tab is where the operator can find details about the operation and recording history of sensor pressure readings and set points.

1.

2.

3.

1. Operation History – Select to view dates and times that various alerts occurred and when they were acknowledged by the operator.

2. Pressure Chart – Click to view recordings of current sensor pressure and setpoints. 3. Pressure Graph – Click to view a graph of current sensor pressure and setpoints.

6

Operation History Page

This page is where the user can view live events that have occurred on the same day. Select the historical button to view events that have occurred in the past.

1.

2.

1. Operation History (Live) – Displays the events that have occurred live on the current date. 2. Historical – Displays events that have happened in the past.

7

Pressure Chart Page This page is where the user can view actual pressure readings and set points for each sensor. This allows the user to verify that pressure set points were not changed during normal operation. It also allows the user to determine how long the filters lasted before needing to be replaced. The data can be exported via USB drive to be imported into Excel as CSV file.

1.

2.

1. Pressure Recording Chart – Displays the sensor pressure reading and set points every five minutes. 2. Export – Follow the on screen instructions on this page to export the data to a USB drive.

8

Pressure Graph Page This page is where the user can view pressure readings stored in the touch screen in a graphical view. The data on this graph is automatically compiled from the data stored in the Pressure Chart screen.

1.

1. Pressure Recording Graph – Displays the sensor pressure reading and set points in graphical form.

9

Settings Tab

This tab is where various system timers and settings can be adjusted. The settings are passcode protected to help prevent unauthorized setting changes.

1.

2.

3.

4.

1. User Level Selection – Dropdown menu so that the operator can select which user is logging in. 2. Enter Passcode – Select this box and a pop-up keypad will allow the operator to enter the passcode for the selected user. 3. Login – Select the login button to confirm login passcode. 4. Next – After the successfully logging in, this button will appear and allow the operator to begin adjusting settings.

Default Passcodes: User Level = 4321 Manager Level = 1234 Maintenance Level = 1111 Admin Level = Contact RTT Tech Support 888-452-6684

10

Settings Launch Page

This page is where the operator can enter various pressure set points, email address with notification settings, delay timers, and screen network settings.

(Previous Screen)

1.

2.

3.

4.

5.

1. Pressure Set Points – Select to enter the desired warning, replace and shutdown pressure set points. 2. Change Passcodes – Available when logged in as Admin. Select to view/change passcodes. 3. Email Settings – Select to enter notification contacts. 4. Timers – Select to enter delay timers for resetting notifications. 5. Date/Time Settings – Select to adjust date/time and network settings within the touchscreen.

11

Filter Pressure Set Points

This page is where the user can enter the desired pressure set points for the warning, replace, and shutdown values.

(Previous Screen)

1.

6.

2.

3. 4. 5.

1. Sensor Name – Select this box to name the sensor. 2. Current Pressure – Displays the value being received from the sensor. 3. Warn Set Point – Enter the desired set point at which the monitor will warn the operator that a filter change is required soon. The yellow light will illuminate when the pressure exceeds this value. Use the spec sheet provided with your filters to determine the proper settings. 4. Replace Set Point – Enter the desired set point at which the monitor will warn the operator that a filter change is required. The red light will illuminate when the pressure exceeds this value. Use the spec sheet provided with your filters to determine the proper settings. 5. Shutdown Set Point – Enter the desired set point at which the monitor will turn off the optional interlock connected to external equipment. The interlock will be turned off when the pressure exceeds this value. The interlock can be used to turn off application equipment or trigger other alarms within the facility. 6. Notification Groups – Select a desired group to be notified via email (active internet connection required) when the pressure exceeds the set point values. Common settings would be: 1. Group A = Coatings Managers & Maintenance Departments

2. Group B = Maintenance & Purchasing Departments 3. Group C = Operation Directors & Facility Managers

12

Change Passcodes This page allows the admin to change passcodes for manager, maintenance, and admin levels of login credentials. Note – RTT Engineered Solutions will not have access to new passcodes – if passcodes are forgotten, an RTT technician will need to assist with resetting the passcodes.

(Previous Screen)

1.

2.

3.

1. Login Level – Select the desired passcode to change. 2. New Passcode – Enter a new passcode into the box. 3. Click Here To Save – Select this button to apply changes to the passcode change.

13

Email Contacts Editor

This page allows the user to enter contact information for various notifications that are enabled from the pressure set points page.

(Previous Screen)

1.

3.

2.

1. Add/Remove Contact – Select the + or – to add or remove a new contact from the list. 2. Group Selection – Select which group to add/remove a contact. 3. Add/Remove Contact to Group – Select the desired contact to add or remove from a group then click the arrow to move into or remove from the selected group.

14

Delay Timers This page allows the user to adjust the amount of time before the system automatically resets. This is used to reduce repeat notifications as the sensor pressure approaches the set point values. Increase the time if you are experiencing too many repeat notifications.

1.

2.

1. Warning Reset Time – This timer is used to automatically reset the notifications if the sensor pressure falls below the warning set point for more than the adjustable time entered. Extending this time will reduce repeat notifications. 2. Replace Reset Time – This timer is used to automatically reset the notifications if the sensor pressure falls below the replace set point for more than the adjustable time entered. Extending this time will reduce repeat notifications.

15

Date/Time & System Settings This page allows the user to adjust the time/date stored within the touchscreen. This menu will also allow the user to input network settings if required. By default the touchscreen is configured to automatically receive network settings from the end user’s DHCP server.

1.

2.

1. Login – Select the lock button to enter the default passcode of 111111 2. Login Successful – After successfully logging in, the lock indicator will be “unlocked” and the menu will be available to adjust time/date and network settings.

16

Date/Time & System Settings

1.

2.

3.

1. Date/Time – Select to input the new date and time settings. 2. Network Settings – Select to view/change network settings such as DHCP, IP Address, Subnet mask, Gateway, and DNS. These settings can be adjusted as needed by the end users Network Administrator. 3. Ethernet 2/Enable Bridge – DO NOT ADJUST THESE SETTINGS WITHOUT RTT APPROVAL. The ethernet 2 port is used to communicate with the PLC and other devices within the control panel. Adjusting these settings will cause communication failures.

17

Certifications

UL Authorization to Mark (UL 508a)

18