North American Solenoid Valves Specifications, Dimensions
Sheet 1400-1
GAS SOLENOID VALVES
Solenoid valves control the flow of manufactured, natural or propane gas in industrial burner systems, for main line, pilot line, and venting applications. They are two-way direct acting and internal pilot operated with 120/60-110/50 standard voltage.
1486BA-0
INSTALLATION
1486G
Valves with a "G" suffix listed below must be mounted with solenoid vertical and upright.
Specifications for Normally Closed Shutoff Valves (UL Listed, FM Approved, and CSA Certified 5 )
coil
max. capacity (cfh)
max.
VA
Valve
pipe orifice press.
0.6 sp gr 1"wc P
recommended backpressure
designation
size
size
psig
class holding inrush
enclosure types
1486A-02 B 1486A-01 B 1486A-0B 1486BA-0
3⁄8 " ½ " ¾ " ¾ " ¾ "
7⁄32 " ¾ " 4 ¾ " 4
100
40
0.5"wc 0.5"wc 0.5"wc 0.5"wc 1.5 psi 1.5 psi 1.5 psi 1.5 psi
F F F F
40 25 25 27
70 70 70
2, 3, 3S, 4, 4X 2, 3, 3S, 4, 4X 2, 3, 3S, 4, 4X
50 50 25 20 20 20 20 20
240 250 580 580
1 5⁄8 " 4
160
2 and 3R
1486G-0 1486G-1 1486G-2 1486G-3 1486G-4
1 5⁄8 " 1 5⁄8 " 1 5⁄8 " 1 5⁄8 "
H H H H H
122 122 122 122 122
600 600 600 600 600
4 4 4 4 4
1" 3 /
1170
4
1 ¼ " 1 ½ "
1660 1870 3250
2" 1 /
2 3⁄32 "
1 psi
2
Notes: 1. Valves listed with the G suffix include Position Indication and FM "Proof-of-Closure" Switch with valve seal overtravel. The switch rating is 15 watts maximum resistive load current not to exceed 1 ampere and the voltage not to exceed 120 volts, AC or DC. 2. For valves listed with the A suffix requiring Class I, Div. 1, Groups (A,B,C,D) and Class II, Div. 1, Groups (E,F,G) - Types 3,3S,4,4X,6,6P, 7, and 9, specify -W at end of product number (1486A-01-W). 3. All valve bodies are aluminum with Buna N seating except 1486A-02 is brass. 4. See page 5 for fluid and ambient temperatures. 5. For 1486 valves requiring CSA certificates order the C1486 -# valves in Oracle.
Made with FlippingBook flipbook maker