PHILIP PAYNE | SINGLE-ZONE SPECTOWEB OVER 64 CONNECTED LUMINAIRES/SIGNS

3A fused unswitched mains supply

3A fused unswitched mains supply

Transmits test results to the SpectoWeb monitoring website

e-mails of test reports sent to authorised personnel

Transmits test results to the SpectoWeb monitoring website

e-mails of test reports sent to authorised personnel

SpectoWeb Controller

SpectoWeb Controller

ata Circuit

WWW

WWW

DALI Data Circuit

DALI Data Circuit

Unswitched Mains Local Lighting Sub-Circuit 1

Unswitched Mains Local Lighting Sub-Circuit 1

SpectoWeb Luminaire

SpectoWeb Luminaire

SpectoWeb Luminaire

SpectoWeb Luminaire

SpectoWeb Luminaire

SpectoWeb Luminaire

Zone 1 Maximum 64 luminaires

Zone 1 does not reqire a separate SZT or SDT

Unswitched Mains Local Lighting Sub Circuit 2

Unswitched Mains Local Lighting Sub Circuit 2

ed

ply

DALI Data Circuit

SpectoWeb Luminaire

SpectoWeb Luminaire

SpectoWeb Luminaire

SpectoWeb Luminaire

SpectoWeb Luminaire

SpectoWeb Luminaire

SpectoWebDistribution Terminal (SDT)

Zone 2 Maximum 30 Luminaires 1 x SDT & SZT required

SpectoWebZone Terminal (SZT)

Unswitched Mains Local Lighting Sub-Circuit 3

Unswitched Mains Local Lighting Sub-Circuit 3

ed

ply

DALI Data Circuit

SpectoWeb Luminaire

SpectoWeb Luminaire

SpectoWeb Luminaire

SpectoWeb Luminaire

SpectoWeb Luminaire

SpectoWeb Luminaire

SpectoWebDistribution Terminal (SDT)

Zone 3 Maximum 30 Luminaires 1 x SDT & SZT required

SpectoWebZone Terminal (SZT)

= Junction Box

= Junction Box • 230V supply cables are 1.5mm² - 2.5mm² • DALI data circuits run directly from SpectoWeb controller to luminaires - DALI cables are 1.0mm² or 1.5mm² two core mains rated (please do not use mains cable colours)

• 230V supply cables are 1.5mm² - 2.5mm² • CANbus data circuit runs from the SpectoWeb Controller to the SDT’s - CANbus cabels are a special specification (please contact Phillip Payne Ltd.) - Maximum total CANbus circuit cabel length = 1000m - CANbus Data Circuits are polarity sensitive - DONOT CROSS CONNECTWIRES

- 1.0mm² = 200mmaximum cable length - 1.5mm² = 300mmaximum cable length - DALI data circuits are non-polarity sensitive

• DALI data circuits run from SDT’s to Luminaires - DALI cabels are 1.0mm² or 1.5mm² two core mains rated (please do not use mains cable colours)

• Maximum 64 luminaires in SINGLE ZONE

- 1.0mm² = 200mmaximum cable length per zone - 1.5mm² = 300mmaximum cable length per zone - DALI data circuits are non-polarity sensitive

• Maximum 50 zones. 1 x SDT and SZT are required per zone (except Zone 1 - no SDT or SZT required) • Maximum 30 luminaires per zone (except Zone 1 - maximum 64 luminaires)