PHILIP PAYNE | SINGLE-ZONE SPECTOWEB OVER 64 CONNECTED LUMINAIRES/SIGNS
3A fused unswitched mains supply
3A fused unswitched mains supply
Transmits test results to the SpectoWeb monitoring website
e-mails of test reports sent to authorised personnel
Transmits test results to the SpectoWeb monitoring website
e-mails of test reports sent to authorised personnel
SpectoWeb Controller
SpectoWeb Controller
ata Circuit
WWW
WWW
DALI Data Circuit
DALI Data Circuit
Unswitched Mains Local Lighting Sub-Circuit 1
Unswitched Mains Local Lighting Sub-Circuit 1
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWeb Luminaire
Zone 1 Maximum 64 luminaires
Zone 1 does not reqire a separate SZT or SDT
Unswitched Mains Local Lighting Sub Circuit 2
Unswitched Mains Local Lighting Sub Circuit 2
ed
ply
DALI Data Circuit
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWebDistribution Terminal (SDT)
Zone 2 Maximum 30 Luminaires 1 x SDT & SZT required
SpectoWebZone Terminal (SZT)
Unswitched Mains Local Lighting Sub-Circuit 3
Unswitched Mains Local Lighting Sub-Circuit 3
ed
ply
DALI Data Circuit
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWebDistribution Terminal (SDT)
Zone 3 Maximum 30 Luminaires 1 x SDT & SZT required
SpectoWebZone Terminal (SZT)
= Junction Box
= Junction Box • 230V supply cables are 1.5mm² - 2.5mm² • DALI data circuits run directly from SpectoWeb controller to luminaires - DALI cables are 1.0mm² or 1.5mm² two core mains rated (please do not use mains cable colours)
• 230V supply cables are 1.5mm² - 2.5mm² • CANbus data circuit runs from the SpectoWeb Controller to the SDT’s - CANbus cabels are a special specification (please contact Phillip Payne Ltd.) - Maximum total CANbus circuit cabel length = 1000m - CANbus Data Circuits are polarity sensitive - DONOT CROSS CONNECTWIRES
- 1.0mm² = 200mmaximum cable length - 1.5mm² = 300mmaximum cable length - DALI data circuits are non-polarity sensitive
• DALI data circuits run from SDT’s to Luminaires - DALI cabels are 1.0mm² or 1.5mm² two core mains rated (please do not use mains cable colours)
• Maximum 64 luminaires in SINGLE ZONE
- 1.0mm² = 200mmaximum cable length per zone - 1.5mm² = 300mmaximum cable length per zone - DALI data circuits are non-polarity sensitive
• Maximum 50 zones. 1 x SDT and SZT are required per zone (except Zone 1 - no SDT or SZT required) • Maximum 30 luminaires per zone (except Zone 1 - maximum 64 luminaires)