195
MULTI-ZONE SPECTOWEB | PHILIP PAYNE UP TO 64 CONNECTED LUMINAIRES/SIGNS
3A fused unswitched mains supply
3A fused unswitched mains supply
Transmits test results to the SpectoWeb monitoring website
e-mails of test reports sent to authorised personnel
Transmits test results to the SpectoWeb monitoring website
e-mails of test reports sent to authorised personnel
SpectoWeb Controller
SpectoWeb Controller
Specto Distribution Terminal
CANbus Data Circuit
WWW
WWW
SpectoController to Luminaire + DALI
DALI Data Circuit
DALI Data Circuit
Mains in
Unswitched Mains Local Lighting Sub-Circuit 1
Unswitched Mains Local Lighting Sub-Circuit 1
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWeb Luminaire
Zone 1 Maximum 64 luminaires
Zone 1 does not reqire a separate SZT or SDT
Unswitched Mains Local Lighting Sub Circuit 2
Unswitched Mains Local Lighting Sub Circuit 2
Unswitched mains supply
RJ45 to SZT
to SpectoController or next SDT
SDT
DALI Data Circuit
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWebDistribution Terminal (SDT)
SDT
Zone 2 Maximum 30 Luminaires 1 x SDT & SZT required
LUMINAIRES - up to 30 per SDT max.
SpectoWebZone Terminal (SZT)
Unswitched Mains Local Lighting Sub-Circuit 3
Unswitched Mains Local Lighting Sub-Circuit 3
Unswitched mains supply
DALI Data Circuit
Specto Zone Terminal
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWeb Luminaire
SpectoWebDistribution Terminal (SDT)
Zone 3 Maximum 30 Luminaires 1 x SDT & SZT required
Key switch
SpectoWebZone Terminal (SZT)
Specto Distribution Unit
= Junction Box
= Junction Box • 230V supply cables are 1.5mm² - 2.5mm² • DALI data circuits run directly from SpectoWeb controller to luminaires - DALI cables are 1.0mm² or 1.5mm² two core mains rated (please do not use mains cable colours)
• 230V supply cables are 1.5mm² - 2.5mm² • CANbus data circuit runs from the SpectoWeb Controller to the SDT’s - CANbus cabels are a special specification (please contact Phillip Payne Ltd.) - Maximum total CANbus circuit cabel length = 1000m - CANbus Data Circuits are polarity sensitive - DONOT CROSS CONNECTWIRES
Specto Zone Terminal
TonextSDT
- 1.0mm² = 200mmaximum cable length - 1.5mm² = 300mmaximum cable length - DALI data circuits are non-polarity sensitive
• DALI data circuits run from SDT’s to Luminaires - DALI cabels are 1.0mm² or 1.5mm² two core mains rated (please do not use mains cable colours)
• Maximum 64 luminaires in SINGLE ZONE
- 1.0mm² = 200mmaximum cable length per zone - 1.5mm² = 300mmaximum cable length per zone - DALI data circuits are non-polarity sensitive
• Maximum 50 zones. 1 x SDT and SZT are required per zone (except Zone 1 - no SDT or SZT required) • Maximum 30 luminaires per zone (except Zone 1 - maximum 64 luminaires)