7.3.1 The b lowe r moto r is t ypically co nfigured t o opera te wi th 208 -230/460 volt, 60 cycles, a nd 3 phase electrical power, unless speci fied o therwise with t he equipmen t orde r. A ma gne tic moto r sta rter is necessary t o p roperly en ergize (el ectrically ) t he u n it. with o ve r load p rotection is a ttached t o t he u n it. The voltage (and full loa d a mps), fo r wh ich the mot or is co nfigured, should b e la beled o n t he electri cal connection bo x. Ele ctrical connections t o t he b o x (and wiri ng) mus t be s ized and se le cted in a ccordance with lo cal, stat e, a nd n ation al codes .
7.3.2 Nomin al Fu ll Lo ad Amp eres a re a s follo ws:
Voltage
Horse Power
208V
230V
460V
575V
10.0
8.0
4.0 6.5 9.0
3.5 5.0 7.0
3
15.00
13.0 18.0
5
20.0
7.5
7.3.3 The b lowe r is d esigned t o r ota te clock wis e wh en v iewed from t he moto r side (top o f blower) . If t he b lowe r is r unnin g in r everse, t he a ir volume will b e a pproximately 50% of the d esigned air volume a nd excessive n oise will b e generat ed . Therefore, o nce the mot o r is wired, che ck moto r rotation by energizing the b lowe r moto r fo r a brief in stan t (“JOG” ). If d irection is reversed , then correct. Switchin g two (2) o f t he 3 -phase connections o n t he o utpu t side will rev erse t he direction o f r otation. 7.3.4 If y ou r un it is eq uipped with t he “Turbo Digital Pu lse Control”, t hen t his fe ature will n eed t o be co nne cted to a 120 v o lt powe r source . Powe r consumption is les s t han 50 Watts.
NOTE: Instructions that detail the operation of Turbo Digital Pulse Control is available under separate cover. A copy of the instructions should have been supplied with the unit.
NOTE: The digital reverse jet pulse controller with “Pulse on Shut down” feature must be wired with a continuous 115 volt supply. The control must not be wired in parallel with the fan motor starter. (Exception is when using an Amtech combination motor starter with disconnect as this has a dedicated 115V transformer.)
7.4 Compressed Air
NOTE: The compressed air installation should be performed by a qualified installer and in accordance with local, state, and national codes/regulations/laws (if any).
7.4.1 Compressed air is u sed t o cle an t he dus t coated ca rtridge fil ters w ith a high pressure reverse j e t pulse . A one in ch diamete r dedicated sup ply wit h a min imum o f 8 0 PSI a nd a maximu m o f 100 PSI is r ecommended. An air re gulato r may b e n ecessary t o s tep d own t he sup ply air if th e p lan t pressure is above t he r ecommended r atin g. N OT co mplyin g will r esu lt in co mponen t damage. 7.4.2 The air s upply lin e t o t he a ccumulato r tan k must include wat er, oil a nd p articulate filtration . Wa ter a nd es pecially oil in t he co mpressed air wi l l s ignificantly r educe the ef fectiveness o f the reverse j e t pulse cle anin g b y co ntaminating the ca rtridge fil ters a nd ca using excessive d ifferentia l pressure a cross t he fi lters, wh ich results in g reatly r educed air f low a lon g wi th p remature filter replacement. 7.4.3 A 200 PSI gage h as b een p re-installed t o mon ito r air pressure . Prio r to t he final connection of t he air lin e t o t he co llecto r manifold, t he air lin e sho uld b e p urged . This will r emove d ebris t hat co uld damage t he v alves a nd b lock t he n ozzles in t he blow p ipes.