Oman Low-Voltage-Power-and-Control-Cables

Authorized distributor of top-quality MEP related products with 7 branches across the UAE.

INDEX

Sl No Description

Table No Page No.

1 Company Profile

3 4 5 6 7 8 9

2 Introduction

3 Cable Construction and Manufacturing Process 4 Notes on FRLS and FR Sheathed Cables

5 Quality

6 Cable Care

7 Drum Handling Instructions

8 XLPE Insulated Power Cables – (Dimensions & Weights)

10 11 11 12 12 13 13 14 14 15 15 16 16 17 17 19 19 20 20 21 21 22 22 23 23 24 24 25 25

Single Core (CU or AL/XLPE/AWA/PVC) Single Core (CU or AL/XLPE/PVC) 2 Core (CU or AL/XLPE/SWA/PVC) 2 Core (CU or AL/XLPE/PVC) 3 Core (CU or AL/XLPE/SWA/PVC) 3 Core (CU or AL/XLPE/PVC) 4 Core (CU or AL/XLPE/SWA/PVC) 4 Core (CU or AL/XLPE/PVC) 3.5 Core (CU or AL/XLPE/SWA/PVC) 3.5 Core (CU or AL/XLPE/PVC) 5 Core (CU or AL/XLPE/SWA/PVC) 5 Core (CU or AL/XLPE/PVC)

1 2 3 4 5 6 7 8 9

10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39

Single Core (CU or AL/XLPE/AWA/PVC)-1.9/3.3(3.6) KV 3 Core (CU or AL/XLPE/SWA/PVC) -1.9/3.3(3.6) KV

9 PVC Insulated Power Cables – (Dimensions & Weights) Single Core (CU or AL/PVC/AWA/PVC)

Single Core (CU or AL/PVC/PVC) 2 Core (CU or AL/PVC/SWA/PVC)

2 Core (CU or AL/PVC/PVC)

3 Core (CU or AL/PVC/SWA/PVC)

3 Core (CU or AL/PVC/PVC)

4 Core (CU or AL/PVC/SWA/PVC)

4 Core (CU or AL/PVC/PVC)

3.5 Core (CU or AL/PVC/SWA/PVC) 3.5 Core (CU or AL/PVC/PVC) 5 Core (CU or AL/PVC/SWA/PVC) 5 Core (CU or AL/PVC/PVC)

Single Core (CU or AL/PVC/AWA/PVC) -1.9/3.3 3 Core (CU or AL/PVC/SWA/PVC) -1.9/3.3

XLPE Insulated CONTROL/AUXILIARY CABLES - 600/1000 V (Dimensions & Weights)

10

26

1.5mm 2 CU/XLPE/SWA/PVC

27 27 28 28 29 29

1.5mm 2 CU/XLPE/PVC

2.5mm 2 CU/XLPE/SWA/PVC

2.5mm 2 CU/XLPE/PVC

4mm 2 CU/AL/XLPE/SWA/PVC

4mm 2 CU/AL/XLPE/PVC

PVC Insulated CONTROL/AUXILIARY CABLES - 600/1000 V (Dimensions & Weights)

11

30

1.5mm 2 CU/PVC/SWA/PVC

31 31 32 32 33

1.5mm 2 CU/PVC/PVC

2.5mm 2 CU/PVC/SWA/PVC 2.5mm 2 CU/PVC/PVC 4mm 2 CU/PVC/SWA/PVC

Sl No Description

Table No Page No.

4mm 2 CU/PVC/PVC

40

33 34

12 Current Ratings of Cables:

Current Ratings & Voltage Drop Of The Cables - 600/1000 V Single Core Copper, XLPE insulated Armoured/Unarmoured Cables. Two Core Copper, XLPE insulated Armoured/Unarmoured Cables. 3 and 4 Core, Copper, XLPE insulated Armoured/Unarmoured Cables. Single Core Aluminium, XLPE insulated Armoured/Unarmoured Cables. Two Core Aluminium, XLPE insulated Armoured/Unarmoured Cables. 3 and 4 Core, Aluminium, XLPE insulated Armoured/Unarmoured Cables. Single Core Copper, PVC insulated Armoured/Unarmoured Cables. Two Core Copper, PVC insulated Armoured/Unarmoured Cables. 3 and 4 Core, Copper, PVC insulated Armoured/Unarmoured Cables. Single Core Aluminium, PVC insulated Armoured/Unarmoured Cables. 2 Core Aluminium, Copper, PVC insulated Armoured/Unarmoured Cables. 3 and 4 Core, Aluminium, PVC insulated Armoured/Unarmoured Cables. Rating Factors For Variation In Ambient Temperature For Cables Laid In Air

41 42 43 44 45 46 47 48 49 50 51 52 53

34 35 36 37 38 39 40 41 42 43 44 45 46

Rating Factors For Variation In Ambient Temperature For Cables Laid Direct In Ground Or In Ducts Rating Factors For Depth Of Laying For Cables Laid Direct In Ground Or In Ducts

54

46

55

46

Rating Factors For Variation In Thermal Resistivity Of Soil For Two Or Three Single-Core Cables Laid Direct In The Ground Rating Factors For Variation In Thermal Resistivity Of Soil For Twin Or Multi Core Cables Laid Direct In The Ground Rating Factors For Variation In Thermal Resistivity Of Soil For Three Single-Core Cables In Ducts Rating Factors For Variation In Thermal Resistivity Of Soil For Twin Or Multi-Core Cables Laid In Single-Way Ducts Group Rating Factors For More Than One Twin Or Multi-Core Armoured Or Unarmoured Cables In Horizontal Formation Laid In Direct Ground. Group Rating Factors For More Than One Circuits Of 3 Single Core Armoured Or Unarmoured Cables In Trefoil Touching,Horizontal Formation Laid In Direct Ground Group Rating Factors For More Than One Twin Or Multi-Core Armoured Or Unarmoured Cables In Horizontal Formation Laid In Single Way Ducts Group Rating Factors For More Than One Circuits Of 3 Single Core Armoured Or Unarmoured Cables In Trefoil Touching ,Horizontal Formation Laid In Single Way Ducts Group Rating Factors For Groups Of More Than One Multi-Core Cable In Air to Be Applied To The Current-Carrying Capacity For One Multi-Core Cable In Free Air Group Rating Factors For Groups Of More Than One Circuit Of Single Core Cables To Be Applied To The Current-Carrying Capacity For One Circuit Of Single-Core Cables In Free Air Maximum D.C. Resistance Of Conductor And Armour For XLPE Insulated Cables Maximum D.C. Resistance Of Conductor And Armour For PVC Insulated Cables A.C. Resistance And Reactance Values For XLPE Insulated Cables A.C. Resistance And Reactance Values For PVC Insulated Cables

56

47

57

47

58

48

59

48

60

49

61

49

62

49

63

49

64

50

65

51

66

52

67

53

68 69

54 55

Short Circuit Current Curves For Copper Conductor XLPE Insulated Cables Short Circuit Current Curves For Copper Conductor PVC Insulated Cables Short Circuit Current Curves For Aluminium Conductor XLPE Insulated Cables Short Circuit Current Curves For Aluminium Conductor PVC Insulated Cables

13

56

14

57

15

58

16

59

Company Profile

The manufacturing facilities are situated within the largest industrial complex in Muscat, The Sultanate of Oman, with its offices and factory presently occupying an area of 135000 sqm with future expansion plans inmind. OCI have equivalent facilities in Sohar, Oman at its Aluminum manufacturing facility and together has a capacity of copper and aluminum of more than 120,000 MT annually. Oman Cables Industry (SAOG) has its offices in Oman, UAE, Qatar, and KSA and has an extensive network of distributors and agents throughout MENA, Asia and Europe.

Oman Cables Industry (SAOG) develops, manufactures and markets a totally integrated variety of electrical products, which include medium voltage power cables, low voltage power and control cables , pilot cables, overhead power transmission line conductors and building wires. OCI offers cables with special features suitable for different types of applications, environmental conditions or as per customer requirement. ƒ ƒ Flame retardant properties ƒ ƒ Low smoke and fume (LSF) properties ƒ ƒ Cables with anti-termite sheaths ƒ ƒ UV resistant outer sheath ƒ ƒ Lead sheath

3

MKK XXS002-02/01-12-2014

INTRODUCTION TO LOW VOLTAGE POWER AND CONTROL CABLES

All cable designs covered in this publication generally conform to BS 5467 or IEC 60502 Part-1 for XLPE and BS 6346 or IEC 60502 Part-1 for PVC insulated cables suitable for working voltages 600/1000 Volts and 3300 Volts. The general types of cables are:

1. XLPE Power Cables (Armoured/Unarmoured)

1. PVC Power Cables (Armoured/Unarmoured)

2. Control or Auxiliary Cables (Armoured/Unarmoured/Screened/Unscreened)

3. Special Category Cables:

OCI alsomanufactures cables conforming to other National or International standards with specific customer requirements. This includes cables with MDPE Sheath, Fire Retardant Cables (FR), Fire Retardant and Low Smoke PVC Sheathed Cables (FRLS), Fire Retardant and Reduced Toxic emission PVC sheathed cables (FRRT). Also, cables with special PVC compound with anti-termite and anti-rodent properties can be supplied upon request. Medium Density Polyethylene (MDPE) Sheathing compound shall meet the requirements of Type ST7 to IEC 60502-1 and Type TS2 as per BS 7655-10.1. All dimensional details of such cables shall be same as the cables as per IEC 60502- 1 and BS 5467.

Based on specific requirement, OCI can also provide copper wire armoured cables or additional tinned copper wires in the armour, swellable tapes under and over armour, steel tape armoured cables etc.

The above cables are supplied in Wooden/Steel drums covered with Lamiflex lagging as a standard practice.

TECHNICAL ADVISORY SERVICES OCI’s staff includes specialist Engineers with wide knowledge and decades of long experience in the field of cables and their applications. The technical expertise and experience is available to all clients in the selection of appropriate cable design/specifications.

4 MKK XXS002-02/01-12-2014

CABLE CONSTRUCTION & MANUFACTURING PROCESS

Conductor

: Copper or Aluminium used for the Conductors obtained in the form of 8.0 mm Copper or 9.5 mm Aluminium rods. After testing, rods are drawn into wires of required sizes. These wires are formed into final Conductor in the stranding machines under strict Quality surveillance. : Cross linked polyethylene compound is insulated over the conductors by extrusion process. The raw materials and thicknesses of Insulation are maintained as per standards and conform to IEC 60502 Part-1 or any other International Standard.

Insulation

The Cores of cables are identified either by colour or by numbers as follows:

No. of cores Identification

Old Colour coding

New Colour coding as per BS

1 2 3 4 5

Red or Black Red & Black

Brown or Blue Brown & Blue

Red, Yellow & Blue

Brown, Black & Grey

Red, Yellow, Blue & Black

Blue, Brown, Black & Grey Blue, Brown, Black, Grey & Y/G

Red, Yellow, Blue, Black & Y/G

6- 61

By numbers

By numbers

Laying up

: The insulated cores are laid up with a right hand, or alternating left & right hand, direction of lay in the sequence of the core numbers or colours. Where necessary non-hygroscopic fillers and binder tape is used to form a compact and reasonably circular cable. : All cables have taped bedding under the lead sheath (Extruded bedding can be provided, if required). The bedding material used is compatible with the operating temperature of Insulation material. Thickness of bedding shall be as per IEC-60502-1.

Bedding

Armour

: When armouring is required, the armour (for multi core cables) consists of single layer of galvanized steel wires/galvanized steel tapes. The armour is applied helically as per standards.

Single core cables are armoured with Aluminium Wires or Copper wires based on requirement. Outer sheath : Standard cables are manufactured with Extruded black PVC Type ST-2 compound of IEC 60502-1. Outer sheath is embossed or printed with the information required by relevant standards.

Special FR, FRLS, FRRT, MDPE compounds are used for outer sheathing of cables, to suit customer’s specific requirements.

5

MKK XXS002-02/01-12-2014

NOTES ON FRLS AND FR SHEATHED CABLES

Oxygen Index (ASTM D 2863) The criterion for burning is presence of percentage of oxygen in air. By mixing oxygen and nitrogen at various percentages this test finds at what percentage of oxygen the standard specimen starts burning. Higher the oxygen index higher the resistance to get ignited. Min. oxygen index shall be 30%. Temperature Index (ASTM D 2863) Temperature index is the temperature at which the oxygen index of the material becomes 21.This test is carried out usually by extrapolation after the oxygen index is measured at various temperatures. Minimum temperature index shall be 250 ºC. Smoke Density (ASTM D 2843) This parameter relates to measuring and observing relative amounts of smoke produced by the burning or decomposition of materials. This test is carried out in accordance with ASTM D 2843. The measurements are made in terms of loss of light transmission through a collected volume of smoke produced under control standardized conditions. Generally requirement by customer is smoke density rating less than 60%. Acid Gas Emission (IEC 60754-1) During burning of cable materials acid gases are evolved especially hydrogen chloride. The gas emission is evaluated in accordance with test method IEC 60754-1, where approximately 1 gm. of the material is pyrolysed at 800 0 C in a combustion tube and resultant gases are analyzed. Flame Retardance (IEC 60332-1) A single cable sample is clamped vertically. The Bunsen or other similar burner is arranged at 45 Degree to the axis of the cable sample, applying flame at 475 mm below to top clamp. The flame is applied for a period of time depending upon the diameter of the cable.

The test requirement is that after all burning has ceased the charred or affected portion shall not have reached within 50 mm from the top clamp.

Flame Retardance Test (IEC 60332 -3) This test is carried out to check flame retardant properties of bunched cables. Three categories of tests namely category "A", "B" and "C" have been defined according to quantity of combustible material available over unit length. Cable pieces are tied on vertical ladder and flame is applied from a horizontal ladder. After the specified time the burner is removed. All parameters are pre defined according to specification. The charred portion is measured and compared with the standards to decide on acceptability.

Special PVC Compounds with Additional Requirements which OCI can provide:

Property

Material

FR

FRLS 30 250 60 20 %

FRRT

Oxygen Index (Min.) Temperature Index (Min.) Smoke Density Rating (Max.) Acid Gas Generation (Max.) Flammability Test*

30 250

30 250 - 17%

- -

IEC 60332-1 and IEC 60332-3-24

IEC 60332-1 and IEC 60332-3-24

IEC 60332-1 and IEC 60332-3-24

* Based on specific request, we can provide compounds which can meet flammability requirements of IEC 60332-3-23 and IEC 60332-3-22

6 MKK XXS002-02/01-12-2014

Oman Cables Quality Assurance

In order to ensure the best quality assurance system, it is extremely desirable to test and inspect the product at each stage of manufacturing including raw materials and finished product.

Oman Cables have the following Quality Assurance System:-

A. B. C.

Raw Materials Inspection In-process inspection Finished product inspection

Raw Materials Inspection: All the raw materials are procured only from internationally approved companies known for their quality products and once the material is received with their product certificate, Oman Cables quality team tests and inspects the same again. Only those materials which meet Oman Cables internal standards are released for production. In-Process Inspection: A team of well experienced and qualified personnel, dedicated to quality, inspects and test all the in-process materials at every stage and materials complies to the specified requirements are only released for next process. Finished Product Inspection: Oman Cables products before leaving ware house undergo the entire applicable tests according to the standard to which it is manufactured.

Routine tests are carried out for conformity to the specifications on 100% cable drums. Sample tests and type tests are carried out at regular intervals as per the applicable standards to conform the product quality.

7

MKK XXS002-02/01-12-2014

CABLE CARE

PRESERVATION/STORING & HANDLING OF CABLE DRUMS

1. STORAGE a. The site chosen for storage of cable drums should be well-drained and should preferably have a concrete surface, which will not cause the drums to sink and so lead to flange rot and cause extreme difficulty in moving the drums. b. The drums should be stored in such a manner as to leave sufficient space between them for air circulation. It is desirable for the drums to stand on battens placed directly under the flanges. c. In no case shall the drums be stored “on the flat side” i.e. with flanges horizontal. d. For drums, overhead shade is not essential except in areas where the rainfall is heavy. e. The cables should however be protected from direct rays of Sun by leaving the battens on or by providing some form of sun shielding. f. Cable ends must be sealed against water ingress at all times. 2 HANDLING a. The drums should be rolled only in the direction of the arrow, indicated on them. b. No cable drums shall be slung except by a bar through the center bore. Also the cable drums shall be stored away from Boilers or Furnaces. c. When unloading the drums from truck, a crane or forklift should be used if available and the drums carefully lifted and deposited on the ground. If crane is not available then the drums should be carefully rolled down a suitably arranged ramp or rail. Under no circumstances should the drums be dropped to the ground, as the shock may cause serious damage to the inner layers of the cables. d. Transportation over long distance, from storage site to work spots – The drums should be mounted on cable drum wheels strong enough to carry the weight of the drums, which are pulled by means of rope, or alternatively they may be mounted on trailer or vehicle with low loading platform for transportation to the destination.

INSTALLATION

OCI cables are suitable for installation in the ground, duct or air as recommended by all standards and specifications. OCI cables are easier to handle and install.

Wherever possible, installation radius should be large than those given below:

Min. of internal bending radius

Type of cable

Overall diameter (D)

mm

mm

Circular Copper conductor, unarmoured

All

6D

Circular Copper conductor armoured

All

6D

Shaped Copper/Aluminium conductor,

All

8D

armoured or unarmoured

8 MKK XXS002-02/01-12-2014

Drum Handling Instructions

Do not lay drums flat on their sides, use proper wedges to prevent drums rolling

Lifting cable drums using crane

Lift drums on fork trucks correctly

Secure drums adequately before transportation

Roll in the direction shown by the arrow

9

MKK XXS002-02/01-12-2014

XLPE INSULATED POWER CABLES CONFORMING TO IEC 60502-1 AND BS 5467

600/1000 VOLTS 1900/3300 VOLTS

10 MKK XXS002-02/01-12-2014

SINGLE CORE CABLES - 600/1000 V DIMENSIONS & WEIGHTS TABLE –1 CU or AL/XLPE/AWA/PVC – BS 5467 CU or AL CONDUCTOR, XLPE INSULATED, AL-WIRE ARMOURED, PVC SHEATHED

Nominal Thickness of Insulation

Nominal Thickness of Extruded Bedding

Nominal Diameter of Armour Wire

Nominal Thickness of Outer Sheath

Approx. Cable

Approx. Cable Weight for AL Cable

Nominal Area of Conductor

Approx. Overall Diameter

Packing Length (Standard)

Weight for CU Cable

mm²

mm mm mm mm mm kg/km kg/km mtrs

50 70 95

1.0 1.1

0.8 0.8

0.9

1.5 1.5

18.0 20.0

625 885

340 475

1000 1000

1.25

1.1

0.8

1.25

1.6

22.0

1160

590

1000

120 150 185 240 300 400 500 630 800

1.2

0.8

1.25

1.6

23.0

1415

695

1000

1.4

1.0

1.6

1.7

26.0

1790

900

1000

1.6

1.0

1.6

1.8

28.0

2180

1070

1000

1.7

1.0

1.6

1.8

31.0

2760

1300

1000

1.8

1.0

1.6

1.9

34.0

3375

1540

500

2.0

1.2

2.0

2.0

38.0

4370

2010

500

2.2

1.2

2.0

2.1

42.0

5400

2435

500

2.4

1.2

2.0

2.2

46.0

6915

3020

500

2.6

1.4

2.5

2.4

52.0

9030

3935

500

1000

2.8

1.4

2.5

2.5

57.0

11015

4730

500

TABLE –2

CU or AL/XLPE/PVC – IEC 60502 PART 1 CU or AL CONDUCTOR, XLPE INSULATED, PVC SHEATHED (UNARMOURED)

Nominal Thickness of Outer Sheath

Approx. Cable

Approx. Cable Weight for AL Cable

Nominal Area of Conductor

Nominal Thickness of Insulation

Approx. Overall Diameter

Packing Length (Standard)

Weight for CU Cable

mm²

mm

mm

mm

kg/km

kg/km

mtrs

1.5 2.5

0.7 0.7

1.4 1.4

6.0 6.5

50 60

-- --

1000 1000

4 6

0.7

1.4

7.0

80

--

1000

0.7

1.4

7.5

100

--

1000

10 16 25 35 50 70 95

0.7

1.4

8.5

145

--

1000

0.7

1.4

9.0

200

105

1000

0.9

1.4

11.0

300

145

1000

0.9

1.4

12.0

395

180

1000

1.0

1.4

13.0

515

230

1000

1.1

1.4

15.0

715

305

1000

1.1

1.5

17.0

970

400

1000

120 150 185 240 300 400 500 630 800

1.2

1.5

19.0

1205

490

1000

1.4

1.6

21.0

1485

595

1000

1.6

1.6

23.0

1845

735

1000

1.7

1.7

26.0

2395

935

1000

1.8

1.8

28.0

2980

1145

1000

2.0

1.9

32.0

3795

1440

500

2.2

2.0

35.0

4765

1800

500

2.4

2.2

40.0

6230

2335

500

2.6 2.8

2.3 2.4

44.0 49.0

8020 9905

2920 3620

500 500

1000

11 MKK XXS002-02/01-12-2014

2 CORE CABLES - 600/1000 V DIMENSIONS & WEIGHTS TABLE –3 CU or AL/XLPE/SWA/PVC – BS 5467 CU or AL CONDUCTOR, XLPE INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED

Nominal Thickness of Insulation

Nominal Thickness of Extruded Bedding

Nominal Diameter of Armour Wire

Nominal Thickness of Outer Sheath

Approx. Cable

Approx. Cable Weight for AL Cable

Nominal Area of Conductor

Approx. Overall Diameter

Packing Length (Standard)

Weight for CU Cable

mm² 1.5 # 2.5 #

mm mm mm mm mm kg/km kg/km mtrs

0.6 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0

0.8 0.8 0.8 0.8 0.8 0.8 0.8 1.0 1.0 1.0 1.2 1.2 1.2 1.4 1.4 1.6 1.6

0.9 0.9 0.9 0.9 0.9

1.3 1.4 1.4 1.4 1.5 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.4 2.5 2.6 2.8

12.5 14.0 15.0 16.0 18.0 20.0 20.0 23.0 25.0 28.0 32.0 34.0 38.0 42.0 49.0 53.0 58.0

265 310 380 455 610 830 975

-- -- -- -- --

1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

4 # 6 #

10 # 16 #

1.25 1.25

635 665 955

25 35 50 70 95

1.6 1.6 1.6 2.0 2.0 2.0 2.5 2.5 2.5 2.5

1385 1705 2220 3050 3655 4340 5590 7080 8540

1135 1395 1900 2200 2550 3355 4130 4830 5710

500 500 500 500 500 500 500

120 150 185 240 300 400

10475

# Circular conductor.

TABLE –4

CU or AL/XLPE/PVC – IEC-60502 Part 1 CU or AL CONDUCTOR, XLPE INSULATED, PVC SHEATHED (UNARMOURED)

Nominal Thickness of Outer Sheath

Approx. Cable

Approx. Cable Weight for AL Cable

Nominal Area of Conductor

Nominal Thickness of Insulation

Approx. Overall Diameter

Packing Length (Standard)

Weight for CU Cable

mm² 1.5 # 2.5 #

mm

mm

mm 10.0 11.0 12.0 13.0 15.0 17.0 16.0 18.0 21.0 23.0 26.0 28.0 32.0 34.0 41.0 45.0 51.0

kg/km

kg/km

mtrs 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.0 2.1 2.2 2.3 2.5 2.7 2.9

125 160 205 265 375 465 620 815

-- -- -- -- --

4 # 6 #

10 # 16 #

270 315 390 495 655 860

25 35 50 70 95

1065 1480 2010 2500 3075 3815 5000 6220 7905

120 150 185 240 300 400

1050 1280 1575 2055 2505 3145

500 500 500 500 500

# Circular conductor.

12 MKK XXS002-02/01-12-2014

3 CORE CABLES - 600/1000 V DIMENSIONS & WEIGHTS TABLE –5 CU or AL/XLPE/SWA/PVC – BS 5467 CU or AL CONDUCTOR, XLPE INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED

Nominal Thickness of Insulation

Nominal Thickness of Extruded Bedding

Nominal Diameter of Armour Wire

Nominal Thickness of Outer Sheath

Approx. Cable

Approx. Cable Weight for AL Cable

Nominal Area of Conductor

Approx. Overall Diameter

Packing Length (Standard)

Weight for CU Cable

mm² 1.5 # 2.5 #

mm mm mm mm mm kg/km kg/km mtrs

0.6 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0

0.8 0.8 0.8 0.8 0.8 0.8

0.9 0.9 0.9 0.9

1.3 1.4 1.4 1.4 1.5 1.6 1.7 1.8 1.8 1.9 2.1 2.2 2.3 2.4 2.6 2.7 2.9

13.0 14.0 15.0 17.0 19.0 21.0 23.0 25.0 28.0 32.0 36.0 40.0 45.0 48.0 54.0 60.0 64.0

295 350 435 530 825

-- -- -- -- --

1000 1000 1000 1000 1000 1000 1000 1000 1000

4 # 6 #

10 # 16 #

1.25 1.25

1025 1450 1815 2270 3005 4160 5045 6475 7705 9705

730 990

25 35 50 70 95

1

1.6 1.6 1.6 1.6 2.0 2.0 2.5 2.5 2.5 2.5 2.5

1.0 1.0 1.0 1.2 1.2 1.4 1.4 1.4 1.6 1.6

1175 1410 1765 2435 2870 3785 4350 5285 6275 7325

500 500 500 500 500 500 500 250

120 150 185 240 300 400

11845 14465

# Circular conductor.

TABLE –6

CU or AL/XLPE/PVC – IEC-60502 Part 1 CU or AL CONDUCTOR, XLPE INSULATED, PVC SHEATHED (UNARMOURED)

Nominal Thickness of Outer Sheath

Approx. Cable

Approx. Cable Weight for AL Cable

Nominal Area of Conductor

Nominal Thickness of Insulation

Approx. Overall Diameter

Packing Length (Standard)

Weight for CU Cable

mm² 1.5 # 2.5 #

mm

mm

mm

kg/km

kg/km

mtrs 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.0 2.1 2.3 2.4 2.6 2.8 3.1

11.0 12.0 13.0 14.0 16.0 18.0 18.0 21.0 23.0 27.0 30.0 34.0 38.0 40.0 47.0 52.0 57.0

145 185 245 325 470 630 885

-- -- -- -- --

4 # 6 #

10 # 16 #

335 425 535 685 925

25 35 50 70 95

1175 1540 2170 2935 3675 4535 5630 7355 9160

1210 1500 1845 2270 2935 3595 4520

120 150 185 240 300 400

500 500 500 500 500 500

11660

# Circular conductor.

13 MKK XXS002-02/01-12-2014

4 CORE CABLES - 600/1000 V DIMENSIONS & WEIGHTS TABLE –7 CU or AL/XLPE/SWA/PVC – BS 5467 CU or AL CONDUCTOR, XLPE INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED

Nominal Thickness of Insulation

Nominal Thickness of Extruded Bedding

Nominal Diameter of Armour Wire

Nominal Thickness of Outer Sheath

Approx. Cable

Approx. Cable Weight for AL Cable

Nominal Area of Conductor

Approx. Overall Diameter

Packing Length (Standard)

Weight for CU Cable

mm² 1.5 # 2.5 #

mm mm mm mm mm kg/km kg/km mtrs

0.6 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0

0.8 0.8 0.8 0.8 0.8 0.8

0.9 0.9 0.9

1.3 1.4 1.4 1.5 1.5 1.6 1.7 1.8 1.9 2.1 2.2 2.3 2.4 2.6 2.7 2.9 3.2

14.0 15.0 16.0 18.0 21.0 23.0 26.0 29.0 31.0 37.0 40.0 47.0 51.0 56.0 62.0 68.0 78.0

330 405 500 730 950

-- -- -- -- --

1000 1000 1000 1000 1000 1000 1000 1000 1000

4 # 6 #

1.25 1.25 1.25

10 # 16 #

1230 1835 2285 2845 4115 5280 6910 8210 9980

840

25 35 50 70 95

1

1.6 1.6 1.6

1225 1435 1705 2460 2975 4010 4620 5500 6645 7740

1.0 1.0 1.2 1.2 1.4 1.4 1.4 1.6 1.6 1.8

2

500 500 500 500 500 250 250 250

2.0 2.5 2.5 2.5 2.5 2.5

120 150 185 240 300 400

12540 15160 19860

3.15

10340

# Circular conductor.

TABLE –8

CU or AL/XLPE/PVC – IEC-60502 Part 1 CU or AL CONDUCTOR, XLPE INSULATED, PVC SHEATHED (UNARMOURED)

Nominal Thickness of Outer Sheath

Approx. Cable

Approx. Cable Weight for AL Cable

Nominal Area of Conductor

Nominal Thickness of Insulation

Approx. Overall Diameter

Packing Length (Standard)

Weight for CU Cable

mm² 1.5 # 2.5 #

mm

mm

mm 11.0 12.0 14.0 15.0 17.0 19.0 21.0 24.0 26.0 30.0 34.0 39.0 43.0 49.0 55.0 60.0 68.0

kg/km

kg/km

mtrs 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9

170 225 300 395 575 805

-- -- -- -- --

4 # 6 #

10 # 16 #

410 550 690 885

25 35 50 70 95

1165 1540 2030 2860 3880 4885 5995 7500 9765

2

1210 1580 1980 2410 3020 3870 4725 5980

2.1 2.3 2.4 2.6 2.8

500 500 500 500 500 500 250

120 150 185 240 300 400

3

12145 15500

3.3

# Circular conductor.

14 MKK XXS002-02/01-12-2014

3 1/2 CORE (4 CORE WITH REDUCED NEUTRAL) CABLES - 600/1000 V DIMENSIONS & WEIGHTS TABLE –9 CU or AL/XLPE/SWA/PVC – IEC-60502 Part 1 CU or AL CONDUCTOR, XLPE INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED

Nominal Thickness of Insulation

Nominal Area of Conductor

Nominal Thickness of Extruded Bedding

Nominal Diameter of Armour Wire

Nominal Thickness of Outer Sheath

Approx. Cable

Approx. Cable Weight for AL Cable

Approx. Overall Diameter

Packing Length (Standard)

Weight for CU Cable

Phase Neutral Phase Neutral mm² mm

mm mm mm mm kg/km kg/km mtrs

25

16 0.9 0.7

1.0

1.6

1.8

26.0

1745

1190

1000

35

16 0.9 0.7

1.0

1.6

1.8

29.0

2105

1370

1000

50

25 1.0 0.9

1.0

1.6

1.9

31.0

2645

1630

1000

70

35 1.1 0.9

1.2

2.0

2.1

37.0

3805

2350

500

95

50 1.1 1.0

1.2

2.0

2.2

40.0

4840

2830

500

120

70 1.2 1.1

1.2

2.0

2.4

46.0

6015

3425

500

150

70 1.4 1.1

1.4

2.5

2.5

51.0

7500

4395

500

185

95 1.6 1.1

1.4

2.5

2.7

57.0

9165

5230

500

240

120 1.7 1.2

1.6

2.5

2.9

63.0

11425

6280

250

300

150 1.8 1.4

1.6

2.5

3.0

68.0

13745

7285

250

400

185 2.0 1.6

1.6

3.15

3.3

77.0

17950

9690

250

TABLE –10

CU or AL/XLPE/PVC – IEC-60502 Part 1 CU or AL CONDUCTOR, XLPE INSULATED, PVC SHEATHED (UNARMOURED)

Nominal Area of Conductor

Nominal Thickness of Insulation

Nominal Thickness of Outer Sheath

Approx. Cable

Approx. Cable Weight for AL Cable

Approx. Overall Diameter

Packing Length (Standard)

Weight for CU Cable

Phase Neutral

Phase Neutral

mm²

mm

mm

mm

kg/km

kg/km

mtrs

25

16

0.9

0.7

1.8

21.0

1075

515

1000

35

16

0.9

0.7

1.8

24.0

1360

625

1000

50

25

1.0

0.9

1.8

26.0

1810

800

1000

70

35

1.1

0.9

1.9

30.0

2535

1085

1000

95

50

1.1

1.0

2.1

34.0

3445

1430

500

120

70

1.2

1.1

2.2

39.0

4395

1805

500

150

70

1.4

1.1

2.3

43.0

5245

2140

500

185

95

1.6

1.1

2.5

49.0

6635

2700

500

240

120

1.7

1.2

2.7

54.0

8595

3445

500

300

150

1.8

1.4

2.9

60.0

10670

4205

500

400

185

2.0

1.6

3.1

68.0

13550

5290

250

15 MKK XXS002-02/01-12-2014

5 CORE CABLES - 600/1000 V DIMENSIONS & WEIGHTS TABLE –11 CU or AL/XLPE/SWA/PVC – BS 5467 CU or AL CONDUCTOR, XLPE INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED

Nominal Thickness of Insulation

Nominal Thickness of Extruded Bedding

Nominal Diameter of Armour Wire

Nominal Thickness of Outer Sheath

Approx. Cable

Approx. Cable Weight for AL Cable

Nominal Area of Conductor

Approx. Overall Diameter

Packing Length (Standard)

Weight for CU Cable

mm²

mm mm mm mm mm kg/km kg/km mtrs

1.5 2.5

0.6 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1

0.8 0.8 0.8 0.8 0.8 1.0 1.0 1.0 1.2 1.2

0.9 0.9 0.9

1.4 1.4 1.5 1.5 1.6 1.7 1.8 1.9 2.0 2.2

15.0 16.0 18.0 20.0 23.0 26.0 30.0 33.0 38.0 43.0

380 460 580 845

-- -- -- -- --

1000 1000 1000 1000 1000 1000 1000

4 6

1.25 1.25

10 16 25 35 50 70

1125 1640 2285 2865 3935 5240

1.6 1.6 1.6 2.0 2.0

1150 1510 1790 2495 3150

500 500 500

TABLE –12

CU or AL/XLPE/PVC – IEC-60502 Part 1 CU or AL CONDUCTOR, XLPE INSULATED, PVC SHEATHED (UNARMOURED)

Nominal Thickness of Outer Sheath

Approx. Cable

Approx. Cable Weight for AL Cable

Nominal Area of Conductor

Nominal Thickness of Insulation

Approx. Overall Diameter

Packing Length (Standard)

Weight for CU Cable

mm²

mm

mm

mm

kg/km

kg/km

mtrs

1.5

0.7

1.8

12.0

200

--

1000

2.5

0.7

1.8

13.0

265

--

1000

4

0.7

1.8

15.0

355

--

1000

6

0.7

1.8

16.0

475

--

1000

10

0.7

1.8

19.0

700

--

1000

16

0.7

1.8

21.0

985

495

1000

25

0.9

1.8

25.0

1500

725

1000

35

0.9

1.8

28.0

1975

900

1000

50

1.0

2.0

32.0

2645

1200

500

70

1.1

2.1

37.0

3725

1640

500

16 MKK XXS002-02/01-12-2014

SINGLE CORE CABLES - 1900/3300 V DIMENSIONS & WEIGHTS TABLE –13 CU or AL/XLPE/AWA/PVC – BS 5467 CU or AL CONDUCTOR, XLPE INSULATED, AL WIRE ARMOURED, PVC SHEATHED

Nominal Thickness of Insulation

Nominal Thickness of Extruded Bedding

Nominal Diameter of Armour Wire

Nominal Thickness of Outer Sheath

Approx. Cable

Approx. Cable Weight for AL Cable

Nominal Area of Conductor

Approx. Overall Diameter

Packing Length (Standard)

Weight for CU Cable

mm²

mm mm mm mm mm kg/km kg/km mtrs

50

2.0

0.8

1.25

1.6

20.0

735

455

1000

70

2.0

0.8

1.25

1.6

22.0

960

550

1000

95

2.0

0.8

1.25

1.6

23.0

1230

660

1000

120

2.0

1.0

1.6

1.7

26.0

1570

850

1000

150

2.0

1.0

1.6

1.7

27.0

1845

960

1000

185

2.0

1.0

1.6

1.8

29.0

2215

1110

1000

240

2.0

1.0

1.6

1.8

32.0

2790

1330

1000

300

2.0

1.0

1.6

1.9

34.0

3400

1565

500

400

2.0

1.2

2.0

2.0

38.0

4370

2010

500

500

2.2

1.2

2.0

2.1

42.0

5400

2435

500

630

2.4

1.2

2.0

2.2

46.0

6915

3020

500

800

2.6

1.4

2.5

2.4

52.0

9030

3935

500

1000

2.8

1.4

2.5

2.5

57.0

11015

4730

500

3 CORE CABLES - 1900/3300 V DIMENSIONS & WEIGHTS TABLE –14 CU or AL/XLPE/SWA/PVC – BS 5467 CU or AL CONDUCTOR, XLPE INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED

Nominal Thickness of Extruded Bedding

Nominal Diameter of Armour Wire

Nominal Thickness of Outer Sheath

Approx. Cable

Approx. Cable Weight for AL Cable

Nominal Area of Conductor

Nominal Thickness of Insulation

Approx. Overall Diameter

Packing Length (Standard)

Weight for CU Cable

mm²

mm

mm mm

mm kg/km kg/km mtrs

16 #

2.0

1.0

1.6

1.8

28.0

1520

1225

1000

25 #

2.0

1.0

1.6

1.8

31.0

1920

1455

1000

35

2.0

1.0

1.6

1.9

30.0

2135

1495

1000

50

2.0

1.2

2.0

2.0

34.0

2840

1980

500

70

2.0

1.2

2.0

2.1

37.0

3585

2345

500

95

2.0

1.2

2.0

2.2

40.0

4490

2760

500

120

2.0

1.4

2.5

2.3

45.0

5815

3635

500

150

2.0

1.4

2.5

2.4

48.0

6765

4075

500

185

2.0

1.4

2.5

2.5

50.0

7915

4555

500

240

2.0

1.6

2.5

2.6

56.0

9920

5495

500

300

2.0

1.6

2.5

2.7

61.0

11950

6385

500

400

2.0

1.6

2.5

2.9

64.0

14465

7325

250

# Circular conductor.

17 MKK XXS002-02/01-12-2014

PVC INSULATED POWER CABLES CONFORMING TO IEC 60502-1 AND BS 6346

600/1000 VOLTS 1900/3300 VOLTS

18 MKK XXS002-02/01-12-2014

SINGLE CORE CABLES - 600/1000 V DIMENSIONS & WEIGHTS TABLE –15 CU or AL/PVC/AWA/PVC – BS 6346 CU or AL CONDUCTOR, PVC INSULATED, AL-WIRE ARMOURED, PVC SHEATHED

Nominal Thickness of Insulation

Nominal Thickness of Extruded Bedding

Nominal Diameter of Armour Wire

Nominal Thickness of Outer Sheath

Approx. Cable

Approx. Cable Weight for AL Cable

Nominal Area of Conductor

Approx. Overall Diameter

Packing Length (Standard)

Weight for CU Cable

mm²

mm mm mm mm mm kg/km kg/km mtrs

50 70 95

1.4 1.4

0.8 0.8

1.25 1.25

1.5 1.6

18.0 20.0

715 940

430 530

1000 1000

1.6

0.8

1.25

1.6

22.0

1235

665

1000

120 150 185 240 300 400 500 630 800

1.6

1.0

1.6

1.7

25.0

1575

855

1000

1.8

1.0

1.6

1.7

26.5

1880

995

1000

2.0

1.0

1.6

1.8

29.0

2280

1170

1000

2.2

1.0

1.6

1.9

32.0

2905

1445

500

2.4

1.0

1.6

1.9

34.5

3540

1705

500

2.6

1.2

2.0

2.1

39.0

4575

2220

500

2.8

1.2

2.0

2.1

42.5

5625

2660

500

2.8

1.2

2.0

2.2

46.5

7160

3240

500

2.8 3.0

1.4 1.4

2.5 2.5

2.4 2.5

52.5 57.0

9240

4140 4975

500 500

1000

11265

TABLE –16

CU or AL/PVC/PVC – IEC-60502 Part 1 CU or AL CONDUCTOR, PVC INSULATED, PVC SHEATHED (UNARMOURED)

Nominal Thickness of Outer Sheath

Approx. Cable

Approx. Cable Weight for AL Cable

Nominal Area of Conductor

Nominal Thickness of Insulation

Approx. Overall Diameter

Packing Length (Standard)

Weight for CU Cable

mm²

mm

mm

mm

kg/km

kg/km

mtrs 1000 1000

1.5 2.5

0.8 0.8

1.4 1.4

7.0 7.5

55 70

-- --

4

1.0

1.4

8.5

95

--

1000

6

1.0

1.4

9.0

120

--

1000

10

1.0

1.4

10.0

165

--

1000

16

1.0

1.4

11.0

220

125

1000

25

1.2

1.4

12.5

325

175

1000

35

1.2

1.4

13.5

420

210

1000

50

1.4

1.4

15.0

555

270

1000

70

1.4

1.4

16.5

760

350

1000

95

1.6

1.5

19.0

1035

465

1000

120

1.6

1.5

20.5

1270

555

1000

150

1.8

1.6

22.5

1560

675

1000

185

2.0

1.7

24.5

1945

835

1000

240

2.2

1.8

27.5

2535

1070

1000

300

2.4

1.9

30.5

3145

1310

1000

400

2.6

2.0

33.5

3985

1630

500

500

2.8

2.1

37.5

4990

2025

500

630

2.8

2.2

41.0

6460

2540

500

800

2.8 3.0

2.3 2.5

45.5 50.5

8225

3125 3885

500 500

1000

10170

19 MKK XXS002-02/01-12-2014

2 CORE CABLES - 600/1000 V DIMENSIONS & WEIGHTS TABLE –17 CU or AL/PVC/SWA/PVC – BS 6346 CU or AL CONDUCTOR, PVC INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED

Nominal Thickness of Insulation

Nominal Thickness of Extruded Bedding

Nominal Diameter of Armour Wire

Nominal Thickness of Outer Sheath

Approx. Cable

Approx. Cable Weight for AL Cable

Nominal Area of Conductor

Approx. Overall Diameter

Packing Length (Standard)

Weight for CU Cable

mm²

mm mm mm mm mm kg/km kg/km mtrs

1.5 # 2.5 #

0.6 0.7

0.8 0.8

0.9 0.9

1.4 1.4

13.0 13.5

290 340

-- --

1000 1000

4 # 6 #

0.8

0.8

0.9

1.4

15.5

440

--

1000

0.8

0.8

0.9

1.5

17.0

535

--

1000

10 # 16 #

1.0

0.8

1.25

1.6

19.5

800

--

1000

1.0

0.8

1.25

1.6

21.5

905

710

1000

25 35 50 70 95

1.2

1.0

1.6

1.7

22.0

1210

905

1000

1.2

1.0

1.6

1.8

24.0

1485

1060

1000

1.4

1.0

1.6

1.9

27.0

1865

1295

1000

1.4

1.0

1.6

1.9

29.5

2355

1530

1000

1.6

1.2

2.0

2.1

34.0

3300

2145

500

120 150 185 240 300 400

1.6

1.2

2.0

2.2

36.0

3875

2425

500

1.8

1.2

2.0

2.3

39.5

4595

2800

500

2.0

1.4

2.5

2.4

43.0

5890

3650

500

2.2

1.4

2.5

2.5

50.5

7495

4535

500

2.4 2.6

1.6 1.6

2.5 2.5

2.7 2.9

55.5 60.5

9040

5330 6235

500 500

10995

# Circular conductor.

TABLE –18

CU or AL/PVC/PVC – IEC-60502 Part 1 CU or AL CONDUCTOR, PVC INSULATED, PVC SHEATHED (UNARMOURED)

Nominal Thickness of Outer Sheath

Approx. Cable

Approx. Cable Weight for AL Cable

Nominal Area of Conductor

Nominal Thickness of Insulation

Approx. Overall Diameter

Packing Length (Standard)

Weight for CU Cable

mm² 1.5 # 2.5 #

mm

mm

mm 11.0 12.0 14.0 15.0 17.0 18.5 18.0 20.0 23.0 25.5 28.5 30.5 34.0 36.5 44.0 48.5 54.0

kg/km

kg/km

mtrs 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

0.8 0.8 1.0 1.0 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 2.6

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.0 2.1 2.2 2.4 2.6 2.7 3.0

140 175 245 315 435 540 680 885

-- -- -- -- --

4 # 6 #

10 # 16 #

345 375 460 590 765

25 35 50 70 95

1160 1590 2160 2650 3250 4040 5305 6560 8335

1010 1200 1460 1800 2350 2845 3575

120 150 185 240 300 400

500 500 500 500 500

# Circular conductor.

20 MKK XXS002-02/01-12-2014

3 CORE CABLES - 600/1000 V DIMENSIONS & WEIGHTS TABLE –19 CU or AL/PVC/SWA/PVC – BS 6346 CU or AL CONDUCTOR, PVC INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED

Nominal Thickness of Insulation

Nominal Thickness of Extruded Bedding

Nominal Diameter of Armour Wire

Nominal Thickness of Outer Sheath

Approx. Cable

Approx. Cable Weight for AL Cable

Nominal Area of Conductor

Approx. Overall Diameter

Packing Length (Standard)

Weight for CU Cable

mm² 1.5 # 2.5 #

mm mm mm mm mm kg/km kg/km mtrs

0.6 0.7 0.8 0.8 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 2.6

0.8 0.8 0.8 0.8 0.8 0.8 1.0 1.0 1.0 1.2 1.2 1.2 1.4 1.4 1.6 1.6 1.6

0.9 0.9 0.9

1.4 1.4 1.4 1.5 1.6 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.4 2.5 2.6 2.8 3.0

13.5 14.0 16.0 18.5 20.5 22.5 24.0 26.5 30.0 34.0 38.0 41.5 47.0 49.5 56.5 62.5 67.0

325 385 510 720 930

-- -- -- -- --

1000 1000 1000 1000 1000 1000 1000 1000 1000

4 # 6 #

1.25 1.25 1.25

10 # 16 #

1120 1575 1965 2475 3470 4460 5345 6845 8125

825

25 35 50 70 95

1.6 1.6 1.6 2.0 2.0 2.0 2.5 2.5 2.5 2.5 2.5

1115 1325 1615 2230 2730 3170 4155 4765 5860 6910 8080

500 500 500 500 500 500 250 250

120 150 185 240 300 400

10295 12475 15220

# Circular conductor.

TABLE –20

CU or AL/PVC/PVC – IEC-60502 Part 1 CU or AL CONDUCTOR, PVC INSULATED, PVC SHEATHED (UNARMOURED)

Nominal Thickness of Outer Sheath

Approx. Cable

Approx. Cable Weight for AL Cable

Nominal Area of Conductor

Nominal Thickness of Insulation

Approx. Overall Diameter

Packing Length (Standard)

Weight for CU Cable

mm² 1.5 # 2.5 #

mm

mm

mm 11.5 12.5 14.5 16.0 18.0 19.5 20.0 22.5 26.0 29.0 33.0 36.5 40.0 43.0 49.5 55.5 60.0

kg/km

kg/km

mtrs 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

0.8 0.8 1.0 1.0 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 2.6

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.0 2.1 2.2 2.3 2.5 2.7 2.9 3.1

165 210 300 385 545 720 970

-- -- -- -- --

4 # 6 #

10 # 16 #

425 510 630 820

25 35 50 70 95

1270 1675 2320 3165 3910 4795 5960 7790 9685

1080 1440 1735 2105 2600 3355 4120 5105

500 500 500 500 500 500 500

120 150 185 240 300 400

12250

# Circular conductor.

21 MKK XXS002-02/01-12-2014

Page 1 Page 2 Page 3 Page 4 Page 5 Page 6 Page 7 Page 8 Page 9 Page 10 Page 11 Page 12 Page 13 Page 14 Page 15 Page 16 Page 17 Page 18 Page 19 Page 20 Page 21 Page 22 Page 23 Page 24 Page 25 Page 26 Page 27 Page 28 Page 29 Page 30 Page 31 Page 32 Page 33 Page 34 Page 35 Page 36 Page 37 Page 38 Page 39 Page 40 Page 41 Page 42 Page 43 Page 44 Page 45 Page 46 Page 47 Page 48 Page 49 Page 50 Page 51 Page 52 Page 53 Page 54 Page 55 Page 56 Page 57 Page 58 Page 59 Page 60 Page 61 Page 62 Page 63 Page 64