INDEX
Sl No Description
Table No Page No.
1 Company Profile
3 4 5 6 7 8 9
2 Introduction
3 Cable Construction and Manufacturing Process 4 Notes on FRLS and FR Sheathed Cables
5 Quality
6 Cable Care
7 Drum Handling Instructions
8 XLPE Insulated Power Cables – (Dimensions & Weights)
10 11 11 12 12 13 13 14 14 15 15 16 16 17 17 19 19 20 20 21 21 22 22 23 23 24 24 25 25
Single Core (CU or AL/XLPE/AWA/PVC) Single Core (CU or AL/XLPE/PVC) 2 Core (CU or AL/XLPE/SWA/PVC) 2 Core (CU or AL/XLPE/PVC) 3 Core (CU or AL/XLPE/SWA/PVC) 3 Core (CU or AL/XLPE/PVC) 4 Core (CU or AL/XLPE/SWA/PVC) 4 Core (CU or AL/XLPE/PVC) 3.5 Core (CU or AL/XLPE/SWA/PVC) 3.5 Core (CU or AL/XLPE/PVC) 5 Core (CU or AL/XLPE/SWA/PVC) 5 Core (CU or AL/XLPE/PVC)
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39
Single Core (CU or AL/XLPE/AWA/PVC)-1.9/3.3(3.6) KV 3 Core (CU or AL/XLPE/SWA/PVC) -1.9/3.3(3.6) KV
9 PVC Insulated Power Cables – (Dimensions & Weights) Single Core (CU or AL/PVC/AWA/PVC)
Single Core (CU or AL/PVC/PVC) 2 Core (CU or AL/PVC/SWA/PVC)
2 Core (CU or AL/PVC/PVC)
3 Core (CU or AL/PVC/SWA/PVC)
3 Core (CU or AL/PVC/PVC)
4 Core (CU or AL/PVC/SWA/PVC)
4 Core (CU or AL/PVC/PVC)
3.5 Core (CU or AL/PVC/SWA/PVC) 3.5 Core (CU or AL/PVC/PVC) 5 Core (CU or AL/PVC/SWA/PVC) 5 Core (CU or AL/PVC/PVC)
Single Core (CU or AL/PVC/AWA/PVC) -1.9/3.3 3 Core (CU or AL/PVC/SWA/PVC) -1.9/3.3
XLPE Insulated CONTROL/AUXILIARY CABLES - 600/1000 V (Dimensions & Weights)
10
26
1.5mm 2 CU/XLPE/SWA/PVC
27 27 28 28 29 29
1.5mm 2 CU/XLPE/PVC
2.5mm 2 CU/XLPE/SWA/PVC
2.5mm 2 CU/XLPE/PVC
4mm 2 CU/AL/XLPE/SWA/PVC
4mm 2 CU/AL/XLPE/PVC
PVC Insulated CONTROL/AUXILIARY CABLES - 600/1000 V (Dimensions & Weights)
11
30
1.5mm 2 CU/PVC/SWA/PVC
31 31 32 32 33
1.5mm 2 CU/PVC/PVC
2.5mm 2 CU/PVC/SWA/PVC 2.5mm 2 CU/PVC/PVC 4mm 2 CU/PVC/SWA/PVC
Sl No Description
Table No Page No.
4mm 2 CU/PVC/PVC
40
33 34
12 Current Ratings of Cables:
Current Ratings & Voltage Drop Of The Cables - 600/1000 V Single Core Copper, XLPE insulated Armoured/Unarmoured Cables. Two Core Copper, XLPE insulated Armoured/Unarmoured Cables. 3 and 4 Core, Copper, XLPE insulated Armoured/Unarmoured Cables. Single Core Aluminium, XLPE insulated Armoured/Unarmoured Cables. Two Core Aluminium, XLPE insulated Armoured/Unarmoured Cables. 3 and 4 Core, Aluminium, XLPE insulated Armoured/Unarmoured Cables. Single Core Copper, PVC insulated Armoured/Unarmoured Cables. Two Core Copper, PVC insulated Armoured/Unarmoured Cables. 3 and 4 Core, Copper, PVC insulated Armoured/Unarmoured Cables. Single Core Aluminium, PVC insulated Armoured/Unarmoured Cables. 2 Core Aluminium, Copper, PVC insulated Armoured/Unarmoured Cables. 3 and 4 Core, Aluminium, PVC insulated Armoured/Unarmoured Cables. Rating Factors For Variation In Ambient Temperature For Cables Laid In Air
41 42 43 44 45 46 47 48 49 50 51 52 53
34 35 36 37 38 39 40 41 42 43 44 45 46
Rating Factors For Variation In Ambient Temperature For Cables Laid Direct In Ground Or In Ducts Rating Factors For Depth Of Laying For Cables Laid Direct In Ground Or In Ducts
54
46
55
46
Rating Factors For Variation In Thermal Resistivity Of Soil For Two Or Three Single-Core Cables Laid Direct In The Ground Rating Factors For Variation In Thermal Resistivity Of Soil For Twin Or Multi Core Cables Laid Direct In The Ground Rating Factors For Variation In Thermal Resistivity Of Soil For Three Single-Core Cables In Ducts Rating Factors For Variation In Thermal Resistivity Of Soil For Twin Or Multi-Core Cables Laid In Single-Way Ducts Group Rating Factors For More Than One Twin Or Multi-Core Armoured Or Unarmoured Cables In Horizontal Formation Laid In Direct Ground. Group Rating Factors For More Than One Circuits Of 3 Single Core Armoured Or Unarmoured Cables In Trefoil Touching,Horizontal Formation Laid In Direct Ground Group Rating Factors For More Than One Twin Or Multi-Core Armoured Or Unarmoured Cables In Horizontal Formation Laid In Single Way Ducts Group Rating Factors For More Than One Circuits Of 3 Single Core Armoured Or Unarmoured Cables In Trefoil Touching ,Horizontal Formation Laid In Single Way Ducts Group Rating Factors For Groups Of More Than One Multi-Core Cable In Air to Be Applied To The Current-Carrying Capacity For One Multi-Core Cable In Free Air Group Rating Factors For Groups Of More Than One Circuit Of Single Core Cables To Be Applied To The Current-Carrying Capacity For One Circuit Of Single-Core Cables In Free Air Maximum D.C. Resistance Of Conductor And Armour For XLPE Insulated Cables Maximum D.C. Resistance Of Conductor And Armour For PVC Insulated Cables A.C. Resistance And Reactance Values For XLPE Insulated Cables A.C. Resistance And Reactance Values For PVC Insulated Cables
56
47
57
47
58
48
59
48
60
49
61
49
62
49
63
49
64
50
65
51
66
52
67
53
68 69
54 55
Short Circuit Current Curves For Copper Conductor XLPE Insulated Cables Short Circuit Current Curves For Copper Conductor PVC Insulated Cables Short Circuit Current Curves For Aluminium Conductor XLPE Insulated Cables Short Circuit Current Curves For Aluminium Conductor PVC Insulated Cables
13
56
14
57
15
58
16
59
Company Profile
The manufacturing facilities are situated within the largest industrial complex in Muscat, The Sultanate of Oman, with its offices and factory presently occupying an area of 135000 sqm with future expansion plans inmind. OCI have equivalent facilities in Sohar, Oman at its Aluminum manufacturing facility and together has a capacity of copper and aluminum of more than 120,000 MT annually. Oman Cables Industry (SAOG) has its offices in Oman, UAE, Qatar, and KSA and has an extensive network of distributors and agents throughout MENA, Asia and Europe.
Oman Cables Industry (SAOG) develops, manufactures and markets a totally integrated variety of electrical products, which include medium voltage power cables, low voltage power and control cables , pilot cables, overhead power transmission line conductors and building wires. OCI offers cables with special features suitable for different types of applications, environmental conditions or as per customer requirement. Flame retardant properties Low smoke and fume (LSF) properties Cables with anti-termite sheaths UV resistant outer sheath Lead sheath
3
MKK XXS002-02/01-12-2014
INTRODUCTION TO LOW VOLTAGE POWER AND CONTROL CABLES
All cable designs covered in this publication generally conform to BS 5467 or IEC 60502 Part-1 for XLPE and BS 6346 or IEC 60502 Part-1 for PVC insulated cables suitable for working voltages 600/1000 Volts and 3300 Volts. The general types of cables are:
1. XLPE Power Cables (Armoured/Unarmoured)
1. PVC Power Cables (Armoured/Unarmoured)
2. Control or Auxiliary Cables (Armoured/Unarmoured/Screened/Unscreened)
3. Special Category Cables:
OCI alsomanufactures cables conforming to other National or International standards with specific customer requirements. This includes cables with MDPE Sheath, Fire Retardant Cables (FR), Fire Retardant and Low Smoke PVC Sheathed Cables (FRLS), Fire Retardant and Reduced Toxic emission PVC sheathed cables (FRRT). Also, cables with special PVC compound with anti-termite and anti-rodent properties can be supplied upon request. Medium Density Polyethylene (MDPE) Sheathing compound shall meet the requirements of Type ST7 to IEC 60502-1 and Type TS2 as per BS 7655-10.1. All dimensional details of such cables shall be same as the cables as per IEC 60502- 1 and BS 5467.
Based on specific requirement, OCI can also provide copper wire armoured cables or additional tinned copper wires in the armour, swellable tapes under and over armour, steel tape armoured cables etc.
The above cables are supplied in Wooden/Steel drums covered with Lamiflex lagging as a standard practice.
TECHNICAL ADVISORY SERVICES OCI’s staff includes specialist Engineers with wide knowledge and decades of long experience in the field of cables and their applications. The technical expertise and experience is available to all clients in the selection of appropriate cable design/specifications.
4 MKK XXS002-02/01-12-2014
CABLE CONSTRUCTION & MANUFACTURING PROCESS
Conductor
: Copper or Aluminium used for the Conductors obtained in the form of 8.0 mm Copper or 9.5 mm Aluminium rods. After testing, rods are drawn into wires of required sizes. These wires are formed into final Conductor in the stranding machines under strict Quality surveillance. : Cross linked polyethylene compound is insulated over the conductors by extrusion process. The raw materials and thicknesses of Insulation are maintained as per standards and conform to IEC 60502 Part-1 or any other International Standard.
Insulation
The Cores of cables are identified either by colour or by numbers as follows:
No. of cores Identification
Old Colour coding
New Colour coding as per BS
1 2 3 4 5
Red or Black Red & Black
Brown or Blue Brown & Blue
Red, Yellow & Blue
Brown, Black & Grey
Red, Yellow, Blue & Black
Blue, Brown, Black & Grey Blue, Brown, Black, Grey & Y/G
Red, Yellow, Blue, Black & Y/G
6- 61
By numbers
By numbers
Laying up
: The insulated cores are laid up with a right hand, or alternating left & right hand, direction of lay in the sequence of the core numbers or colours. Where necessary non-hygroscopic fillers and binder tape is used to form a compact and reasonably circular cable. : All cables have taped bedding under the lead sheath (Extruded bedding can be provided, if required). The bedding material used is compatible with the operating temperature of Insulation material. Thickness of bedding shall be as per IEC-60502-1.
Bedding
Armour
: When armouring is required, the armour (for multi core cables) consists of single layer of galvanized steel wires/galvanized steel tapes. The armour is applied helically as per standards.
Single core cables are armoured with Aluminium Wires or Copper wires based on requirement. Outer sheath : Standard cables are manufactured with Extruded black PVC Type ST-2 compound of IEC 60502-1. Outer sheath is embossed or printed with the information required by relevant standards.
Special FR, FRLS, FRRT, MDPE compounds are used for outer sheathing of cables, to suit customer’s specific requirements.
5
MKK XXS002-02/01-12-2014
NOTES ON FRLS AND FR SHEATHED CABLES
Oxygen Index (ASTM D 2863) The criterion for burning is presence of percentage of oxygen in air. By mixing oxygen and nitrogen at various percentages this test finds at what percentage of oxygen the standard specimen starts burning. Higher the oxygen index higher the resistance to get ignited. Min. oxygen index shall be 30%. Temperature Index (ASTM D 2863) Temperature index is the temperature at which the oxygen index of the material becomes 21.This test is carried out usually by extrapolation after the oxygen index is measured at various temperatures. Minimum temperature index shall be 250 ºC. Smoke Density (ASTM D 2843) This parameter relates to measuring and observing relative amounts of smoke produced by the burning or decomposition of materials. This test is carried out in accordance with ASTM D 2843. The measurements are made in terms of loss of light transmission through a collected volume of smoke produced under control standardized conditions. Generally requirement by customer is smoke density rating less than 60%. Acid Gas Emission (IEC 60754-1) During burning of cable materials acid gases are evolved especially hydrogen chloride. The gas emission is evaluated in accordance with test method IEC 60754-1, where approximately 1 gm. of the material is pyrolysed at 800 0 C in a combustion tube and resultant gases are analyzed. Flame Retardance (IEC 60332-1) A single cable sample is clamped vertically. The Bunsen or other similar burner is arranged at 45 Degree to the axis of the cable sample, applying flame at 475 mm below to top clamp. The flame is applied for a period of time depending upon the diameter of the cable.
The test requirement is that after all burning has ceased the charred or affected portion shall not have reached within 50 mm from the top clamp.
Flame Retardance Test (IEC 60332 -3) This test is carried out to check flame retardant properties of bunched cables. Three categories of tests namely category "A", "B" and "C" have been defined according to quantity of combustible material available over unit length. Cable pieces are tied on vertical ladder and flame is applied from a horizontal ladder. After the specified time the burner is removed. All parameters are pre defined according to specification. The charred portion is measured and compared with the standards to decide on acceptability.
Special PVC Compounds with Additional Requirements which OCI can provide:
Property
Material
FR
FRLS 30 250 60 20 %
FRRT
Oxygen Index (Min.) Temperature Index (Min.) Smoke Density Rating (Max.) Acid Gas Generation (Max.) Flammability Test*
30 250
30 250 - 17%
- -
IEC 60332-1 and IEC 60332-3-24
IEC 60332-1 and IEC 60332-3-24
IEC 60332-1 and IEC 60332-3-24
* Based on specific request, we can provide compounds which can meet flammability requirements of IEC 60332-3-23 and IEC 60332-3-22
6 MKK XXS002-02/01-12-2014
Oman Cables Quality Assurance
In order to ensure the best quality assurance system, it is extremely desirable to test and inspect the product at each stage of manufacturing including raw materials and finished product.
Oman Cables have the following Quality Assurance System:-
A. B. C.
Raw Materials Inspection In-process inspection Finished product inspection
Raw Materials Inspection: All the raw materials are procured only from internationally approved companies known for their quality products and once the material is received with their product certificate, Oman Cables quality team tests and inspects the same again. Only those materials which meet Oman Cables internal standards are released for production. In-Process Inspection: A team of well experienced and qualified personnel, dedicated to quality, inspects and test all the in-process materials at every stage and materials complies to the specified requirements are only released for next process. Finished Product Inspection: Oman Cables products before leaving ware house undergo the entire applicable tests according to the standard to which it is manufactured.
Routine tests are carried out for conformity to the specifications on 100% cable drums. Sample tests and type tests are carried out at regular intervals as per the applicable standards to conform the product quality.
7
MKK XXS002-02/01-12-2014
CABLE CARE
PRESERVATION/STORING & HANDLING OF CABLE DRUMS
1. STORAGE a. The site chosen for storage of cable drums should be well-drained and should preferably have a concrete surface, which will not cause the drums to sink and so lead to flange rot and cause extreme difficulty in moving the drums. b. The drums should be stored in such a manner as to leave sufficient space between them for air circulation. It is desirable for the drums to stand on battens placed directly under the flanges. c. In no case shall the drums be stored “on the flat side” i.e. with flanges horizontal. d. For drums, overhead shade is not essential except in areas where the rainfall is heavy. e. The cables should however be protected from direct rays of Sun by leaving the battens on or by providing some form of sun shielding. f. Cable ends must be sealed against water ingress at all times. 2 HANDLING a. The drums should be rolled only in the direction of the arrow, indicated on them. b. No cable drums shall be slung except by a bar through the center bore. Also the cable drums shall be stored away from Boilers or Furnaces. c. When unloading the drums from truck, a crane or forklift should be used if available and the drums carefully lifted and deposited on the ground. If crane is not available then the drums should be carefully rolled down a suitably arranged ramp or rail. Under no circumstances should the drums be dropped to the ground, as the shock may cause serious damage to the inner layers of the cables. d. Transportation over long distance, from storage site to work spots – The drums should be mounted on cable drum wheels strong enough to carry the weight of the drums, which are pulled by means of rope, or alternatively they may be mounted on trailer or vehicle with low loading platform for transportation to the destination.
INSTALLATION
OCI cables are suitable for installation in the ground, duct or air as recommended by all standards and specifications. OCI cables are easier to handle and install.
Wherever possible, installation radius should be large than those given below:
Min. of internal bending radius
Type of cable
Overall diameter (D)
mm
mm
Circular Copper conductor, unarmoured
All
6D
Circular Copper conductor armoured
All
6D
Shaped Copper/Aluminium conductor,
All
8D
armoured or unarmoured
8 MKK XXS002-02/01-12-2014
Drum Handling Instructions
Do not lay drums flat on their sides, use proper wedges to prevent drums rolling
Lifting cable drums using crane
Lift drums on fork trucks correctly
Secure drums adequately before transportation
Roll in the direction shown by the arrow
9
MKK XXS002-02/01-12-2014
XLPE INSULATED POWER CABLES CONFORMING TO IEC 60502-1 AND BS 5467
600/1000 VOLTS 1900/3300 VOLTS
10 MKK XXS002-02/01-12-2014
SINGLE CORE CABLES - 600/1000 V DIMENSIONS & WEIGHTS TABLE –1 CU or AL/XLPE/AWA/PVC – BS 5467 CU or AL CONDUCTOR, XLPE INSULATED, AL-WIRE ARMOURED, PVC SHEATHED
Nominal Thickness of Insulation
Nominal Thickness of Extruded Bedding
Nominal Diameter of Armour Wire
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Nominal Area of Conductor
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
mm²
mm mm mm mm mm kg/km kg/km mtrs
50 70 95
1.0 1.1
0.8 0.8
0.9
1.5 1.5
18.0 20.0
625 885
340 475
1000 1000
1.25
1.1
0.8
1.25
1.6
22.0
1160
590
1000
120 150 185 240 300 400 500 630 800
1.2
0.8
1.25
1.6
23.0
1415
695
1000
1.4
1.0
1.6
1.7
26.0
1790
900
1000
1.6
1.0
1.6
1.8
28.0
2180
1070
1000
1.7
1.0
1.6
1.8
31.0
2760
1300
1000
1.8
1.0
1.6
1.9
34.0
3375
1540
500
2.0
1.2
2.0
2.0
38.0
4370
2010
500
2.2
1.2
2.0
2.1
42.0
5400
2435
500
2.4
1.2
2.0
2.2
46.0
6915
3020
500
2.6
1.4
2.5
2.4
52.0
9030
3935
500
1000
2.8
1.4
2.5
2.5
57.0
11015
4730
500
TABLE –2
CU or AL/XLPE/PVC – IEC 60502 PART 1 CU or AL CONDUCTOR, XLPE INSULATED, PVC SHEATHED (UNARMOURED)
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Nominal Area of Conductor
Nominal Thickness of Insulation
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
mm²
mm
mm
mm
kg/km
kg/km
mtrs
1.5 2.5
0.7 0.7
1.4 1.4
6.0 6.5
50 60
-- --
1000 1000
4 6
0.7
1.4
7.0
80
--
1000
0.7
1.4
7.5
100
--
1000
10 16 25 35 50 70 95
0.7
1.4
8.5
145
--
1000
0.7
1.4
9.0
200
105
1000
0.9
1.4
11.0
300
145
1000
0.9
1.4
12.0
395
180
1000
1.0
1.4
13.0
515
230
1000
1.1
1.4
15.0
715
305
1000
1.1
1.5
17.0
970
400
1000
120 150 185 240 300 400 500 630 800
1.2
1.5
19.0
1205
490
1000
1.4
1.6
21.0
1485
595
1000
1.6
1.6
23.0
1845
735
1000
1.7
1.7
26.0
2395
935
1000
1.8
1.8
28.0
2980
1145
1000
2.0
1.9
32.0
3795
1440
500
2.2
2.0
35.0
4765
1800
500
2.4
2.2
40.0
6230
2335
500
2.6 2.8
2.3 2.4
44.0 49.0
8020 9905
2920 3620
500 500
1000
11 MKK XXS002-02/01-12-2014
2 CORE CABLES - 600/1000 V DIMENSIONS & WEIGHTS TABLE –3 CU or AL/XLPE/SWA/PVC – BS 5467 CU or AL CONDUCTOR, XLPE INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED
Nominal Thickness of Insulation
Nominal Thickness of Extruded Bedding
Nominal Diameter of Armour Wire
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Nominal Area of Conductor
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
mm² 1.5 # 2.5 #
mm mm mm mm mm kg/km kg/km mtrs
0.6 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0
0.8 0.8 0.8 0.8 0.8 0.8 0.8 1.0 1.0 1.0 1.2 1.2 1.2 1.4 1.4 1.6 1.6
0.9 0.9 0.9 0.9 0.9
1.3 1.4 1.4 1.4 1.5 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.4 2.5 2.6 2.8
12.5 14.0 15.0 16.0 18.0 20.0 20.0 23.0 25.0 28.0 32.0 34.0 38.0 42.0 49.0 53.0 58.0
265 310 380 455 610 830 975
-- -- -- -- --
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
4 # 6 #
10 # 16 #
1.25 1.25
635 665 955
25 35 50 70 95
1.6 1.6 1.6 2.0 2.0 2.0 2.5 2.5 2.5 2.5
1385 1705 2220 3050 3655 4340 5590 7080 8540
1135 1395 1900 2200 2550 3355 4130 4830 5710
500 500 500 500 500 500 500
120 150 185 240 300 400
10475
# Circular conductor.
TABLE –4
CU or AL/XLPE/PVC – IEC-60502 Part 1 CU or AL CONDUCTOR, XLPE INSULATED, PVC SHEATHED (UNARMOURED)
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Nominal Area of Conductor
Nominal Thickness of Insulation
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
mm² 1.5 # 2.5 #
mm
mm
mm 10.0 11.0 12.0 13.0 15.0 17.0 16.0 18.0 21.0 23.0 26.0 28.0 32.0 34.0 41.0 45.0 51.0
kg/km
kg/km
mtrs 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.0 2.1 2.2 2.3 2.5 2.7 2.9
125 160 205 265 375 465 620 815
-- -- -- -- --
4 # 6 #
10 # 16 #
270 315 390 495 655 860
25 35 50 70 95
1065 1480 2010 2500 3075 3815 5000 6220 7905
120 150 185 240 300 400
1050 1280 1575 2055 2505 3145
500 500 500 500 500
# Circular conductor.
12 MKK XXS002-02/01-12-2014
3 CORE CABLES - 600/1000 V DIMENSIONS & WEIGHTS TABLE –5 CU or AL/XLPE/SWA/PVC – BS 5467 CU or AL CONDUCTOR, XLPE INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED
Nominal Thickness of Insulation
Nominal Thickness of Extruded Bedding
Nominal Diameter of Armour Wire
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Nominal Area of Conductor
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
mm² 1.5 # 2.5 #
mm mm mm mm mm kg/km kg/km mtrs
0.6 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0
0.8 0.8 0.8 0.8 0.8 0.8
0.9 0.9 0.9 0.9
1.3 1.4 1.4 1.4 1.5 1.6 1.7 1.8 1.8 1.9 2.1 2.2 2.3 2.4 2.6 2.7 2.9
13.0 14.0 15.0 17.0 19.0 21.0 23.0 25.0 28.0 32.0 36.0 40.0 45.0 48.0 54.0 60.0 64.0
295 350 435 530 825
-- -- -- -- --
1000 1000 1000 1000 1000 1000 1000 1000 1000
4 # 6 #
10 # 16 #
1.25 1.25
1025 1450 1815 2270 3005 4160 5045 6475 7705 9705
730 990
25 35 50 70 95
1
1.6 1.6 1.6 1.6 2.0 2.0 2.5 2.5 2.5 2.5 2.5
1.0 1.0 1.0 1.2 1.2 1.4 1.4 1.4 1.6 1.6
1175 1410 1765 2435 2870 3785 4350 5285 6275 7325
500 500 500 500 500 500 500 250
120 150 185 240 300 400
11845 14465
# Circular conductor.
TABLE –6
CU or AL/XLPE/PVC – IEC-60502 Part 1 CU or AL CONDUCTOR, XLPE INSULATED, PVC SHEATHED (UNARMOURED)
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Nominal Area of Conductor
Nominal Thickness of Insulation
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
mm² 1.5 # 2.5 #
mm
mm
mm
kg/km
kg/km
mtrs 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.0 2.1 2.3 2.4 2.6 2.8 3.1
11.0 12.0 13.0 14.0 16.0 18.0 18.0 21.0 23.0 27.0 30.0 34.0 38.0 40.0 47.0 52.0 57.0
145 185 245 325 470 630 885
-- -- -- -- --
4 # 6 #
10 # 16 #
335 425 535 685 925
25 35 50 70 95
1175 1540 2170 2935 3675 4535 5630 7355 9160
1210 1500 1845 2270 2935 3595 4520
120 150 185 240 300 400
500 500 500 500 500 500
11660
# Circular conductor.
13 MKK XXS002-02/01-12-2014
4 CORE CABLES - 600/1000 V DIMENSIONS & WEIGHTS TABLE –7 CU or AL/XLPE/SWA/PVC – BS 5467 CU or AL CONDUCTOR, XLPE INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED
Nominal Thickness of Insulation
Nominal Thickness of Extruded Bedding
Nominal Diameter of Armour Wire
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Nominal Area of Conductor
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
mm² 1.5 # 2.5 #
mm mm mm mm mm kg/km kg/km mtrs
0.6 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0
0.8 0.8 0.8 0.8 0.8 0.8
0.9 0.9 0.9
1.3 1.4 1.4 1.5 1.5 1.6 1.7 1.8 1.9 2.1 2.2 2.3 2.4 2.6 2.7 2.9 3.2
14.0 15.0 16.0 18.0 21.0 23.0 26.0 29.0 31.0 37.0 40.0 47.0 51.0 56.0 62.0 68.0 78.0
330 405 500 730 950
-- -- -- -- --
1000 1000 1000 1000 1000 1000 1000 1000 1000
4 # 6 #
1.25 1.25 1.25
10 # 16 #
1230 1835 2285 2845 4115 5280 6910 8210 9980
840
25 35 50 70 95
1
1.6 1.6 1.6
1225 1435 1705 2460 2975 4010 4620 5500 6645 7740
1.0 1.0 1.2 1.2 1.4 1.4 1.4 1.6 1.6 1.8
2
500 500 500 500 500 250 250 250
2.0 2.5 2.5 2.5 2.5 2.5
120 150 185 240 300 400
12540 15160 19860
3.15
10340
# Circular conductor.
TABLE –8
CU or AL/XLPE/PVC – IEC-60502 Part 1 CU or AL CONDUCTOR, XLPE INSULATED, PVC SHEATHED (UNARMOURED)
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Nominal Area of Conductor
Nominal Thickness of Insulation
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
mm² 1.5 # 2.5 #
mm
mm
mm 11.0 12.0 14.0 15.0 17.0 19.0 21.0 24.0 26.0 30.0 34.0 39.0 43.0 49.0 55.0 60.0 68.0
kg/km
kg/km
mtrs 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9
170 225 300 395 575 805
-- -- -- -- --
4 # 6 #
10 # 16 #
410 550 690 885
25 35 50 70 95
1165 1540 2030 2860 3880 4885 5995 7500 9765
2
1210 1580 1980 2410 3020 3870 4725 5980
2.1 2.3 2.4 2.6 2.8
500 500 500 500 500 500 250
120 150 185 240 300 400
3
12145 15500
3.3
# Circular conductor.
14 MKK XXS002-02/01-12-2014
3 1/2 CORE (4 CORE WITH REDUCED NEUTRAL) CABLES - 600/1000 V DIMENSIONS & WEIGHTS TABLE –9 CU or AL/XLPE/SWA/PVC – IEC-60502 Part 1 CU or AL CONDUCTOR, XLPE INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED
Nominal Thickness of Insulation
Nominal Area of Conductor
Nominal Thickness of Extruded Bedding
Nominal Diameter of Armour Wire
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
Phase Neutral Phase Neutral mm² mm
mm mm mm mm kg/km kg/km mtrs
25
16 0.9 0.7
1.0
1.6
1.8
26.0
1745
1190
1000
35
16 0.9 0.7
1.0
1.6
1.8
29.0
2105
1370
1000
50
25 1.0 0.9
1.0
1.6
1.9
31.0
2645
1630
1000
70
35 1.1 0.9
1.2
2.0
2.1
37.0
3805
2350
500
95
50 1.1 1.0
1.2
2.0
2.2
40.0
4840
2830
500
120
70 1.2 1.1
1.2
2.0
2.4
46.0
6015
3425
500
150
70 1.4 1.1
1.4
2.5
2.5
51.0
7500
4395
500
185
95 1.6 1.1
1.4
2.5
2.7
57.0
9165
5230
500
240
120 1.7 1.2
1.6
2.5
2.9
63.0
11425
6280
250
300
150 1.8 1.4
1.6
2.5
3.0
68.0
13745
7285
250
400
185 2.0 1.6
1.6
3.15
3.3
77.0
17950
9690
250
TABLE –10
CU or AL/XLPE/PVC – IEC-60502 Part 1 CU or AL CONDUCTOR, XLPE INSULATED, PVC SHEATHED (UNARMOURED)
Nominal Area of Conductor
Nominal Thickness of Insulation
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
Phase Neutral
Phase Neutral
mm²
mm
mm
mm
kg/km
kg/km
mtrs
25
16
0.9
0.7
1.8
21.0
1075
515
1000
35
16
0.9
0.7
1.8
24.0
1360
625
1000
50
25
1.0
0.9
1.8
26.0
1810
800
1000
70
35
1.1
0.9
1.9
30.0
2535
1085
1000
95
50
1.1
1.0
2.1
34.0
3445
1430
500
120
70
1.2
1.1
2.2
39.0
4395
1805
500
150
70
1.4
1.1
2.3
43.0
5245
2140
500
185
95
1.6
1.1
2.5
49.0
6635
2700
500
240
120
1.7
1.2
2.7
54.0
8595
3445
500
300
150
1.8
1.4
2.9
60.0
10670
4205
500
400
185
2.0
1.6
3.1
68.0
13550
5290
250
15 MKK XXS002-02/01-12-2014
5 CORE CABLES - 600/1000 V DIMENSIONS & WEIGHTS TABLE –11 CU or AL/XLPE/SWA/PVC – BS 5467 CU or AL CONDUCTOR, XLPE INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED
Nominal Thickness of Insulation
Nominal Thickness of Extruded Bedding
Nominal Diameter of Armour Wire
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Nominal Area of Conductor
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
mm²
mm mm mm mm mm kg/km kg/km mtrs
1.5 2.5
0.6 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1
0.8 0.8 0.8 0.8 0.8 1.0 1.0 1.0 1.2 1.2
0.9 0.9 0.9
1.4 1.4 1.5 1.5 1.6 1.7 1.8 1.9 2.0 2.2
15.0 16.0 18.0 20.0 23.0 26.0 30.0 33.0 38.0 43.0
380 460 580 845
-- -- -- -- --
1000 1000 1000 1000 1000 1000 1000
4 6
1.25 1.25
10 16 25 35 50 70
1125 1640 2285 2865 3935 5240
1.6 1.6 1.6 2.0 2.0
1150 1510 1790 2495 3150
500 500 500
TABLE –12
CU or AL/XLPE/PVC – IEC-60502 Part 1 CU or AL CONDUCTOR, XLPE INSULATED, PVC SHEATHED (UNARMOURED)
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Nominal Area of Conductor
Nominal Thickness of Insulation
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
mm²
mm
mm
mm
kg/km
kg/km
mtrs
1.5
0.7
1.8
12.0
200
--
1000
2.5
0.7
1.8
13.0
265
--
1000
4
0.7
1.8
15.0
355
--
1000
6
0.7
1.8
16.0
475
--
1000
10
0.7
1.8
19.0
700
--
1000
16
0.7
1.8
21.0
985
495
1000
25
0.9
1.8
25.0
1500
725
1000
35
0.9
1.8
28.0
1975
900
1000
50
1.0
2.0
32.0
2645
1200
500
70
1.1
2.1
37.0
3725
1640
500
16 MKK XXS002-02/01-12-2014
SINGLE CORE CABLES - 1900/3300 V DIMENSIONS & WEIGHTS TABLE –13 CU or AL/XLPE/AWA/PVC – BS 5467 CU or AL CONDUCTOR, XLPE INSULATED, AL WIRE ARMOURED, PVC SHEATHED
Nominal Thickness of Insulation
Nominal Thickness of Extruded Bedding
Nominal Diameter of Armour Wire
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Nominal Area of Conductor
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
mm²
mm mm mm mm mm kg/km kg/km mtrs
50
2.0
0.8
1.25
1.6
20.0
735
455
1000
70
2.0
0.8
1.25
1.6
22.0
960
550
1000
95
2.0
0.8
1.25
1.6
23.0
1230
660
1000
120
2.0
1.0
1.6
1.7
26.0
1570
850
1000
150
2.0
1.0
1.6
1.7
27.0
1845
960
1000
185
2.0
1.0
1.6
1.8
29.0
2215
1110
1000
240
2.0
1.0
1.6
1.8
32.0
2790
1330
1000
300
2.0
1.0
1.6
1.9
34.0
3400
1565
500
400
2.0
1.2
2.0
2.0
38.0
4370
2010
500
500
2.2
1.2
2.0
2.1
42.0
5400
2435
500
630
2.4
1.2
2.0
2.2
46.0
6915
3020
500
800
2.6
1.4
2.5
2.4
52.0
9030
3935
500
1000
2.8
1.4
2.5
2.5
57.0
11015
4730
500
3 CORE CABLES - 1900/3300 V DIMENSIONS & WEIGHTS TABLE –14 CU or AL/XLPE/SWA/PVC – BS 5467 CU or AL CONDUCTOR, XLPE INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED
Nominal Thickness of Extruded Bedding
Nominal Diameter of Armour Wire
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Nominal Area of Conductor
Nominal Thickness of Insulation
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
mm²
mm
mm mm
mm kg/km kg/km mtrs
16 #
2.0
1.0
1.6
1.8
28.0
1520
1225
1000
25 #
2.0
1.0
1.6
1.8
31.0
1920
1455
1000
35
2.0
1.0
1.6
1.9
30.0
2135
1495
1000
50
2.0
1.2
2.0
2.0
34.0
2840
1980
500
70
2.0
1.2
2.0
2.1
37.0
3585
2345
500
95
2.0
1.2
2.0
2.2
40.0
4490
2760
500
120
2.0
1.4
2.5
2.3
45.0
5815
3635
500
150
2.0
1.4
2.5
2.4
48.0
6765
4075
500
185
2.0
1.4
2.5
2.5
50.0
7915
4555
500
240
2.0
1.6
2.5
2.6
56.0
9920
5495
500
300
2.0
1.6
2.5
2.7
61.0
11950
6385
500
400
2.0
1.6
2.5
2.9
64.0
14465
7325
250
# Circular conductor.
17 MKK XXS002-02/01-12-2014
PVC INSULATED POWER CABLES CONFORMING TO IEC 60502-1 AND BS 6346
600/1000 VOLTS 1900/3300 VOLTS
18 MKK XXS002-02/01-12-2014
SINGLE CORE CABLES - 600/1000 V DIMENSIONS & WEIGHTS TABLE –15 CU or AL/PVC/AWA/PVC – BS 6346 CU or AL CONDUCTOR, PVC INSULATED, AL-WIRE ARMOURED, PVC SHEATHED
Nominal Thickness of Insulation
Nominal Thickness of Extruded Bedding
Nominal Diameter of Armour Wire
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Nominal Area of Conductor
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
mm²
mm mm mm mm mm kg/km kg/km mtrs
50 70 95
1.4 1.4
0.8 0.8
1.25 1.25
1.5 1.6
18.0 20.0
715 940
430 530
1000 1000
1.6
0.8
1.25
1.6
22.0
1235
665
1000
120 150 185 240 300 400 500 630 800
1.6
1.0
1.6
1.7
25.0
1575
855
1000
1.8
1.0
1.6
1.7
26.5
1880
995
1000
2.0
1.0
1.6
1.8
29.0
2280
1170
1000
2.2
1.0
1.6
1.9
32.0
2905
1445
500
2.4
1.0
1.6
1.9
34.5
3540
1705
500
2.6
1.2
2.0
2.1
39.0
4575
2220
500
2.8
1.2
2.0
2.1
42.5
5625
2660
500
2.8
1.2
2.0
2.2
46.5
7160
3240
500
2.8 3.0
1.4 1.4
2.5 2.5
2.4 2.5
52.5 57.0
9240
4140 4975
500 500
1000
11265
TABLE –16
CU or AL/PVC/PVC – IEC-60502 Part 1 CU or AL CONDUCTOR, PVC INSULATED, PVC SHEATHED (UNARMOURED)
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Nominal Area of Conductor
Nominal Thickness of Insulation
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
mm²
mm
mm
mm
kg/km
kg/km
mtrs 1000 1000
1.5 2.5
0.8 0.8
1.4 1.4
7.0 7.5
55 70
-- --
4
1.0
1.4
8.5
95
--
1000
6
1.0
1.4
9.0
120
--
1000
10
1.0
1.4
10.0
165
--
1000
16
1.0
1.4
11.0
220
125
1000
25
1.2
1.4
12.5
325
175
1000
35
1.2
1.4
13.5
420
210
1000
50
1.4
1.4
15.0
555
270
1000
70
1.4
1.4
16.5
760
350
1000
95
1.6
1.5
19.0
1035
465
1000
120
1.6
1.5
20.5
1270
555
1000
150
1.8
1.6
22.5
1560
675
1000
185
2.0
1.7
24.5
1945
835
1000
240
2.2
1.8
27.5
2535
1070
1000
300
2.4
1.9
30.5
3145
1310
1000
400
2.6
2.0
33.5
3985
1630
500
500
2.8
2.1
37.5
4990
2025
500
630
2.8
2.2
41.0
6460
2540
500
800
2.8 3.0
2.3 2.5
45.5 50.5
8225
3125 3885
500 500
1000
10170
19 MKK XXS002-02/01-12-2014
2 CORE CABLES - 600/1000 V DIMENSIONS & WEIGHTS TABLE –17 CU or AL/PVC/SWA/PVC – BS 6346 CU or AL CONDUCTOR, PVC INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED
Nominal Thickness of Insulation
Nominal Thickness of Extruded Bedding
Nominal Diameter of Armour Wire
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Nominal Area of Conductor
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
mm²
mm mm mm mm mm kg/km kg/km mtrs
1.5 # 2.5 #
0.6 0.7
0.8 0.8
0.9 0.9
1.4 1.4
13.0 13.5
290 340
-- --
1000 1000
4 # 6 #
0.8
0.8
0.9
1.4
15.5
440
--
1000
0.8
0.8
0.9
1.5
17.0
535
--
1000
10 # 16 #
1.0
0.8
1.25
1.6
19.5
800
--
1000
1.0
0.8
1.25
1.6
21.5
905
710
1000
25 35 50 70 95
1.2
1.0
1.6
1.7
22.0
1210
905
1000
1.2
1.0
1.6
1.8
24.0
1485
1060
1000
1.4
1.0
1.6
1.9
27.0
1865
1295
1000
1.4
1.0
1.6
1.9
29.5
2355
1530
1000
1.6
1.2
2.0
2.1
34.0
3300
2145
500
120 150 185 240 300 400
1.6
1.2
2.0
2.2
36.0
3875
2425
500
1.8
1.2
2.0
2.3
39.5
4595
2800
500
2.0
1.4
2.5
2.4
43.0
5890
3650
500
2.2
1.4
2.5
2.5
50.5
7495
4535
500
2.4 2.6
1.6 1.6
2.5 2.5
2.7 2.9
55.5 60.5
9040
5330 6235
500 500
10995
# Circular conductor.
TABLE –18
CU or AL/PVC/PVC – IEC-60502 Part 1 CU or AL CONDUCTOR, PVC INSULATED, PVC SHEATHED (UNARMOURED)
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Nominal Area of Conductor
Nominal Thickness of Insulation
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
mm² 1.5 # 2.5 #
mm
mm
mm 11.0 12.0 14.0 15.0 17.0 18.5 18.0 20.0 23.0 25.5 28.5 30.5 34.0 36.5 44.0 48.5 54.0
kg/km
kg/km
mtrs 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
0.8 0.8 1.0 1.0 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 2.6
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.0 2.1 2.2 2.4 2.6 2.7 3.0
140 175 245 315 435 540 680 885
-- -- -- -- --
4 # 6 #
10 # 16 #
345 375 460 590 765
25 35 50 70 95
1160 1590 2160 2650 3250 4040 5305 6560 8335
1010 1200 1460 1800 2350 2845 3575
120 150 185 240 300 400
500 500 500 500 500
# Circular conductor.
20 MKK XXS002-02/01-12-2014
3 CORE CABLES - 600/1000 V DIMENSIONS & WEIGHTS TABLE –19 CU or AL/PVC/SWA/PVC – BS 6346 CU or AL CONDUCTOR, PVC INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED
Nominal Thickness of Insulation
Nominal Thickness of Extruded Bedding
Nominal Diameter of Armour Wire
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Nominal Area of Conductor
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
mm² 1.5 # 2.5 #
mm mm mm mm mm kg/km kg/km mtrs
0.6 0.7 0.8 0.8 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 2.6
0.8 0.8 0.8 0.8 0.8 0.8 1.0 1.0 1.0 1.2 1.2 1.2 1.4 1.4 1.6 1.6 1.6
0.9 0.9 0.9
1.4 1.4 1.4 1.5 1.6 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.4 2.5 2.6 2.8 3.0
13.5 14.0 16.0 18.5 20.5 22.5 24.0 26.5 30.0 34.0 38.0 41.5 47.0 49.5 56.5 62.5 67.0
325 385 510 720 930
-- -- -- -- --
1000 1000 1000 1000 1000 1000 1000 1000 1000
4 # 6 #
1.25 1.25 1.25
10 # 16 #
1120 1575 1965 2475 3470 4460 5345 6845 8125
825
25 35 50 70 95
1.6 1.6 1.6 2.0 2.0 2.0 2.5 2.5 2.5 2.5 2.5
1115 1325 1615 2230 2730 3170 4155 4765 5860 6910 8080
500 500 500 500 500 500 250 250
120 150 185 240 300 400
10295 12475 15220
# Circular conductor.
TABLE –20
CU or AL/PVC/PVC – IEC-60502 Part 1 CU or AL CONDUCTOR, PVC INSULATED, PVC SHEATHED (UNARMOURED)
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Nominal Area of Conductor
Nominal Thickness of Insulation
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
mm² 1.5 # 2.5 #
mm
mm
mm 11.5 12.5 14.5 16.0 18.0 19.5 20.0 22.5 26.0 29.0 33.0 36.5 40.0 43.0 49.5 55.5 60.0
kg/km
kg/km
mtrs 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
0.8 0.8 1.0 1.0 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 2.6
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.0 2.1 2.2 2.3 2.5 2.7 2.9 3.1
165 210 300 385 545 720 970
-- -- -- -- --
4 # 6 #
10 # 16 #
425 510 630 820
25 35 50 70 95
1270 1675 2320 3165 3910 4795 5960 7790 9685
1080 1440 1735 2105 2600 3355 4120 5105
500 500 500 500 500 500 500
120 150 185 240 300 400
12250
# Circular conductor.
21 MKK XXS002-02/01-12-2014
Page 1 Page 2 Page 3 Page 4 Page 5 Page 6 Page 7 Page 8 Page 9 Page 10 Page 11 Page 12 Page 13 Page 14 Page 15 Page 16 Page 17 Page 18 Page 19 Page 20 Page 21 Page 22 Page 23 Page 24 Page 25 Page 26 Page 27 Page 28 Page 29 Page 30 Page 31 Page 32 Page 33 Page 34 Page 35 Page 36 Page 37 Page 38 Page 39 Page 40 Page 41 Page 42 Page 43 Page 44 Page 45 Page 46 Page 47 Page 48 Page 49 Page 50 Page 51 Page 52 Page 53 Page 54 Page 55 Page 56 Page 57 Page 58 Page 59 Page 60 Page 61 Page 62 Page 63 Page 64Made with FlippingBook Annual report