page content text Technical Support Control Systems

Customer Power Requirement Worksheet – Option A Delta 3-Phase Power 240 VAC It is the customer’s responsibility to make sure his Hot Runner Mold Application will not exceed the power limitations of the DME Hot Runner Control System Main Circuit Breaker. Even though each slot may be rated at 15 amps, all slots CANNOT necessarily deliver full power from all zones simultaneously. PHASE A POWER PHASE B POWER PHASE C POWER ZONE # WATTAGE ZONE # WATTAGE ZONE # WATTAGE 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 TOTAL PHASE A WATTS TOTAL PHASE B WATTS TOTAL PHASE C WATTS

Record Product Breaker Size Phase Wattage Not To Exceed

Record Product Breaker Size Phase Wattage Not To Exceed

Record Product Breaker Size Phase Wattage Not To Exceed

Breaker Wattage Size Table – For Delta 240 VAC 3-Phase Power

MAXIMUM PHASE WATTS EACH PHASE A,B,C CANNOT EXCEED THIS VALUE

MAXIMUM PHASE AMPS EACH PHASE A,B,C CANNOT EXCEED THIS VALUE

BREAKER RATING AMPS

10 AMP 20 AMP 30 AMP 40 AMP 50 AMP 63 AMP 70 AMP 100 AMP

1,386 WATTS 2,771 WATTS 4,157 WATTS 5,542 WATTS 6,928 WATTS 8,729 WATTS 9,699 WATTS 13,856 WATTS

5.77 AMPS 11.55 AMPS 17.32 AMPS 23.09 AMPS 28.87 AMPS 36.27 AMPS 40.41 AMPS 57.74 AMPS

For 3 Phase Delta Power: TOTAL WATTS = SquareRoot (3) x VoltsAC x AMPS

MAXIMUM PHASE WATTS = TOTAL WATTS / 3